Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2016, 07:17 AM
  • 19 0258_19 0257_8302016_002432.mp4

Date
08/30/2016
W/O
0585465
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00728
PipeID
P15227
Time
12:17 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0260
Sewer Name
19 STUDEBAKER ROAD TRUNK
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
01
Purpose
Routine Assessment
Project
20160829MDM_STUDEBAKER_ROAD_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
19 0257
Downstream MH
19 0256
Dir. of Survey
Downstream
Length Surveyed
333.8 ft.
Total Length
333.8 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 19 0257 to 19 0256
MH: 19 0257MH: 19 0256downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:20AM0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area1 ft. MGO - General Observation - MH# 258 LOCATED ON MAP AT MH# 259 LOCATION14 ft. MGO - General Observation - 15" VCP31.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped78.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped134.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped181.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped229.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active234.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE234.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT234.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE277.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped333.8 ft. AMH - Downstream Manhole, Survey Ends - 12:50AM

Observation photos (1)

  • General Observation - 15" VCP

    14 ft. - General Observation - 15" VCP

Observations (15)

DistanceCodeObservation
229.1TFActive
31.4TFCCapped
234.2FCHAIRLINE
78.9TFCCapped
333.8AMH12:50AM
0AMH12:20AM
134.6TFCCapped
234.1FCHAIRLINE
1MGOMH# 258 LOCATED ON MAP AT MH# 259 LOCATION
0MWM
14MGO15" VCP
0MWL
234.1FLSLIGHT
181.4TFCCapped
277.6TFCCapped

Properties (6)

custom_field_three
1 SLIGHT LONG FRACTURE
custom_field_two
4
customer
LACSD
datetime
2016-08-30T00:17:49-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false