Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 29, 2016, 08:37 AM
  • 19 0260_19 0259_8292016_035557.mp4

Date
08/29/2016
W/O
0585465
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00728
PipeID
P15230
Time
1:37 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0259
Sewer Name
19 STUDEBAKER ROAD TRUNK
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
01
Purpose
Routine Assessment
Project
20160829MDM_STUDEBAKER_ROAD_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
19 0260
Downstream MH
19 0259
Dir. of Survey
Downstream
Length Surveyed
331.7 ft.
Total Length
331.7 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 19 0260 to 19 0259
MH: 19 0260MH: 19 0259downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:55AM0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area8 ft. DAGS - Deposits Attached Grease, 3 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start17 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped27 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE70.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped119 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped166.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped220.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped242.7 ft. DAGS - Deposits Attached Grease, 3 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish242.7 ft. MGO - General Observation - 15" VCP242.7 ft. DAGS - Deposits Attached Grease, 4 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start268.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped303 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - HAIRLINE322.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped331.3 ft. DAGS - Deposits Attached Grease, 4 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish331.7 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observation photos (2)

  • Deposits Attached Grease, 3 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    8 ft. - Deposits Attached Grease, 3 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 15" VCP

    242.7 ft. - General Observation - 15" VCP

Observations (18)

DistanceCodeObservation
242.7DAGS
331.7AMH4:25AM
0AMH3:55AM
17TFCCapped
119TFCCapped
0MWL
331.3DAGS
220.4TFCCapped
268.5TFCCapped
303FLHAIRLINE
0MWM
166.3TFCCapped
242.7MGO15" VCP
322.2TFCCapped
27FCHAIRLINE
70.6TFCCapped
242.7DAGS
8DAGS

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2016-08-29T01:37:28-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false