Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 29, 2016, 08:36 AM
  • 19 0261_19 0260_8292016_024046.mp4

Date
08/29/2016
W/O
0585465
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00728
PipeID
P15231
Time
1:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0259
Sewer Name
19 STUDEBAKER ROAD TRUNK
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
01
Purpose
Routine Assessment
Project
20160829MDM_STUDEBAKER_ROAD_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
19 0261
Downstream MH
19 0260
Dir. of Survey
Downstream
Length Surveyed
224.8 ft.
Total Length
224.8 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 19 0261 to 19 0260
MH: 19 0261MH: 19 0260downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:10AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area11.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE30.3 ft. DAGS - Deposits Attached Grease, 3 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start92.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped140.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped181.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT194.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped207.7 ft. MGO - General Observation - 15" VCP224.3 ft. DAGS - Deposits Attached Grease, 3 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish224.8 ft. AMH - Downstream Manhole, Survey Ends - 2:35AM

Observation photos (2)

  • Deposits Attached Grease, 3 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    30.3 ft. - Deposits Attached Grease, 3 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 15" VCP

    207.7 ft. - General Observation - 15" VCP

Observations (13)

DistanceCodeObservation
92.9TFCCapped
140.8TFCCapped
0AMH2:10AM
224.8AMH2:35AM
224.3DAGS
194.8TFCCapped
30.3DAGS
0MGOConn. @ Mh, 3 O' Clock. Active
0MWL
207.7MGO15" VCP
11.7FCHAIRLINE
0MWM
181.6FLSLIGHT

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2016-08-29T01:36:29-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection