Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 28, 2016, 02:06 PM
  • 19 0041_19 0040_8282016_070756.mp4

Date
08/28/2016
W/O
0585475
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00725
PipeID
P15071
Time
7:06 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7216
Sewer Name
19 FULLERTON ROAD TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
09
Purpose
Routine Assessment
Project
20160828AM_FULLERTON_ROAD_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
19 0040
Downstream MH
19 0041
Dir. of Survey
Upstream
Length Surveyed
156.9 ft.
Total Length
156.9 ft.
Structural Index
3
Structural Quick
5333
Structural Rating
29
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
33
Pipe schematic from manhole 19 0040 to 19 0041
MH: 19 0040MH: 19 0041upstream0 ft. AMH - Upstream Manhole, Survey Ends - 7:27 AM1.4 ft. MGO - General Observation - ROACHES INSIDE THE MH.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2 ft. MGO - General Observation - SLIGHT TO MODERATE GREASE THROUGHOUT THE REACH8.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"9.6 ft. JSM - Joint Separated Medium9.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 10 to 04 o'clock, , within 8 inches of joint: YES9.9 ft. B - Broken, from 08 to 01 o'clock, within 8 inches of joint: YES25 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES25 ft. MGO - General Observation - CHIPPING35.3 ft. B - Broken, from 02 to 04 o'clock, within 8 inches of joint: YES57.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"73.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES89.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES109.8 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES111.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"117.6 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES143.4 ft. B - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES - POSSIBLE155 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start156.9 ft. MWL - Water Level, 15 %of cross sectional area156.9 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK156.9 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK156.9 ft. MGO - General Observation - ROACHES INSIDE THE MH.156.9 ft. MWM - Water Mark, 20 %of cross sectional area156.9 ft. AMH - Downstream Manhole, Survey Begins - 7:06 AM

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Broken, from 08 to 10 o'clock, within 8 inches of joint: YES - POSSIBLE

    13.5 ft. - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES - POSSIBLE

  • Broken, from 02 to 04 o'clock, within 8 inches of joint: YES

    121.6 ft. - Broken, from 02 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - CHIPPING

    131.9 ft. - General Observation - CHIPPING

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 10 to 04 o'clock,  , within 8 inches of joint: YES

    147 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 10 to 04 o'clock, , within 8 inches of joint: YES

  • Broken, from 08 to 01 o'clock, within 8 inches of joint: YES

    147 ft. - Broken, from 08 to 01 o'clock, within 8 inches of joint: YES

  • Joint Separated Medium

    147.3 ft. - Joint Separated Medium

Observations (25)

DistanceCodeObservation
147DAE
155.5MGOROACHES INSIDE THE MH.
0MWL
67.7CM
147B
0MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
13.5BPOSSIBLE
39.3CM
47.1CL
1.9DAGS
156.9AMH7:27 AM
131.9CM
154.9DAGS
99.4TFC
83CL
148.4TFC
121.6B
0MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
45.7TFC
147.3JSM
131.9MGOCHIPPING
154.9MGOSLIGHT TO MODERATE GREASE THROUGHOUT THE REACH
0MGOROACHES INSIDE THE MH.
0MWM
0AMH7:06 AM

Properties (6)

custom_field_three
BROKEN PIPE
custom_field_two
1
customer
LACSD
datetime
2016-08-28T07:06:03-07:00
documentation
MIRANDA & BRAR
is_lateral_inspection
false