Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 27, 2016, 10:01 AM
  • 19 0232_19 0231A_8272016_032054.mp4

Date
08/27/2016
W/O
0585415
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00729
PipeID
P15202
Time
3:01 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
HO256
Sewer Name
19 WEST ARTESIA TRUNK
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
01
Purpose
Routine Assessment
Project
20160827MDM_WEST_ARTESIA_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
19 0232
Downstream MH
19 0231A
Dir. of Survey
Downstream
Length Surveyed
69.9 ft.
Total Length
69.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 19 0232 to 19 0231A
MH: 19 0232MH: 19 0231Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:20AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active8.9 ft. MGO - General Observation - 12" VCP20.3 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open 100% ROOTS33.5 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open 90% ROOTS69.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active69.9 ft. AMH - Downstream Manhole, Survey Ends - 3:35AM

Observation photos (1)

  • General Observation - 12" VCP

    8.9 ft. - General Observation - 12" VCP

Observations (9)

DistanceCodeObservation
0AMH3:20AM
0MWL
33.5TFDOpen 90% ROOTS
69.9AMH3:35AM
8.9MGO12" VCP
69.5MGOConn. @ Mh, 9 O' Clock. Active
0MWM
20.3TFDOpen 100% ROOTS
0MGOConn. @ Mh, 3 O' Clock. Active

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2016-08-27T03:01:53-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false