Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2016, 10:25 AM
  • 05 0454_05 0111_8262016_050416.mp4

Date
08/26/2016
W/O
0585478
Weather
Dry
Operator/Surveyor
MARTIM
Sewer ID
Z00526
PipeID
P05668
Time
3:25 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0253
Sewer Name
05 STRAWBERRY AVENUE TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
20160826MDM_STRAWBERRY_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
05 0454
Downstream MH
05 0111
Dir. of Survey
Downstream
Length Surveyed
318.3 ft.
Total Length
318.3 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 05 0454 to 05 0111
MH: 05 0454MH: 05 0111downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:05AM0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area40.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open 80% GREASE43.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 01 to 04 o'clock, , within 8 inches of joint: YES43.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active93.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN95.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open123.4 ft. MGO - General Observation - 12" VCP143 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open145.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open193.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped195.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open220.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped245.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped283.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES295.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped297.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active301.5 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE318 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active318 ft. MGO - General Observation - LINE DOES NOT PASS THOUGH MH318 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active318.3 ft. AMH - Downstream Manhole, Survey Ends - 5:40AM

Observation photos (1)

  • General Observation - 12" VCP

    123.4 ft. - General Observation - 12" VCP

Observations (23)

DistanceCodeObservation
40.8TFDOpen 80% GREASE
145.6TFOpen
143TFOpen
301.5FCHAIRLINE
297.8TFActive
318MGOConn. @ Mh, 3 O' Clock. Active
93.1TFOPEN
43.7DAGS
95.9TFOpen
318MGOLINE DOES NOT PASS THOUGH MH
193.1TFCCapped
195.5TFOpen
123.4MGO12" VCP
220.9TFCCapped
318.3AMH5:40AM
283.7CL
245.7TFCCapped
43.7TFActive
0AMH5:05AM
295.2TFCCapped
0MWL
318MGOConn. @ Mh, 9 O' Clock. Active
0MWM

Properties (6)

custom_field_three
1 CIRCUM HAIRLINE
custom_field_two
4
customer
LACSD
datetime
2016-08-26T03:25:12-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false