Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2016, 08:01 PM
  • 16 0548_16 0547_8242016_130456.mp4

Date
08/24/2016
W/O
0585428
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00659
PipeID
P13599
Time
1:01 PM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7213
Sewer Name
16 LAMANDA PARK TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
15
Purpose
Routine Assessment
Project
20160824AM_LAMANDA_PARK_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
16 0548
Downstream MH
16 0547
Dir. of Survey
Downstream
Length Surveyed
261 ft.
Total Length
261 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 16 0548 to 16 0547
MH: 16 0548MH: 16 0547downstream0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:02 PM15.8 ft. MGP - General Photograph - MAG COAT PEELING/FLAKING15.8 ft. MGO - General Observation - TAPE FROM THE LINER HANGING90.5 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: NO, UNKNOWN DIAMETER - OPEN, UNSEALED, 50% BLOCKED90.5 ft. RMC - Roots Medium Connection, from 11 to 01 o'clock, 20 %, within 8 inches of joint: NO160.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4" - UNSEALED259.4 ft. MGO - General Observation - WRINKLES THROUGHOUT THE REACH259.4 ft. MGO - General Observation - MAG COAT PEELING/FLAKING THROUGHOUT THE REACH259.4 ft. MGO - General Observation - SLIGHT GREASE/DEBRIS THROUGHOUT THE REACH261 ft. AMH - Downstream Manhole, Survey Ends - 1:28 PM

Observation photos (5)

  • Water Mark, 35 %of cross sectional area

    0 ft. - Water Mark, 35 %of cross sectional area

  • General Photograph - MAG COAT PEELING/FLAKING

    15.8 ft. - General Photograph - MAG COAT PEELING/FLAKING

  • General Observation - TAPE FROM THE LINER HANGING

    15.8 ft. - General Observation - TAPE FROM THE LINER HANGING

  • Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: NO, UNKNOWN DIAMETER - OPEN, UNSEALED, 50% BLOCKED

    90.5 ft. - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: NO, UNKNOWN DIAMETER - OPEN, UNSEALED, 50% BLOCKED

  • Roots Medium Connection, from 11 to 01 o'clock, 20 %, within 8 inches of joint: NO

    90.5 ft. - Roots Medium Connection, from 11 to 01 o'clock, 20 %, within 8 inches of joint: NO

Observations (15)

DistanceCodeObservation
259.4MGOWRINKLES THROUGHOUT THE REACH
15.8MGPMAG COAT PEELING/FLAKING
0MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
90.5TFDOPEN, UNSEALED, 50% BLOCKED
0MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
0MWL
15.8MGOTAPE FROM THE LINER HANGING
259.4MGOMAG COAT PEELING/FLAKING THROUGHOUT THE REACH
0MGOROACHES INSIDE THE MH.
160.2TFAUNSEALED
261AMH1:28 PM
259.4MGOSLIGHT GREASE/DEBRIS THROUGHOUT THE REACH
90.5RMC
0MWM
0AMH1:02 PM

Properties (7)

custom_field_three
PIPE IS LINED
custom_field_two
4
customer
LACSD
datetime
2016-08-24T13:01:08-07:00
documentation
MIRANDA, SHADLER, FRANKLIN
is_lateral_inspection
false
lining
CIPP