Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 23, 2016, 07:49 PM
  • 02 1924_02 1923_8232016_125304.mp4

Date
08/23/2016
W/O
0585839
Weather
Very Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00238
PipeID
P04272
Time
12:49 PM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7212
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
05
Purpose
Capital Improvement Program Assesment
Project
20160823AM_BELVEDERE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1924
Downstream MH
02 1923
Dir. of Survey
Downstream
Length Surveyed
246.4 ft.
Total Length
246.4 ft.
Structural Index
2
Structural Quick
5141
Structural Rating
46
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
46
Pipe schematic from manhole 02 1924 to 02 1923
MH: 02 1924MH: 02 1923downstream0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. AMH - Upstream Manhole, Survey Begins - 12:52 PM0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area23 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN38.4 ft. JSM - Joint Separated Medium38.4 ft. JOL - Joint Offset Large43.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES44.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"44.9 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: NO, Start48.6 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: NO, Finish48.7 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES48.7 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN48.7 ft. JSM - Joint Separated Medium49.7 ft. CM - Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: NO59.1 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES79.6 ft. B - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES79.6 ft. MGP - General Photograph - BROKEN PIPE90.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES95.3 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES100.6 ft. CM - Crack Multiple, from 02 to 10 o'clock, within 8 inches of joint: YES105.6 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES146.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES162.3 ft. MGO - General Observation - CHIPPING187.8 ft. JOM - Joint Offset Medium187.9 ft. JSM - Joint Separated Medium226.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"240 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES244.9 ft. MGO - General Observation - SAGS THROUGHOUT THE REACH244.9 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH245.1 ft. MGO - General Observation - ROACHES INSIDE THE MH.246.4 ft. AMH - Downstream Manhole, Survey Ends - 1:23 PM

Observation photos (16)

  • Water Level, 30 %of cross sectional area

    0 ft. - Water Level, 30 %of cross sectional area

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    23 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Joint Separated Medium

    38.4 ft. - Joint Separated Medium

  • Joint Offset Large

    38.4 ft. - Joint Offset Large

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    43.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: NO, Start

    44.9 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: NO, Start

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: NO, Finish

    48.6 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: NO, Finish

  • Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    48.7 ft. - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Joint Separated Medium

    48.7 ft. - Joint Separated Medium

  • Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: NO

    49.7 ft. - Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: NO

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    59.1 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 10 o'clock, within 8 inches of joint: YES

    79.6 ft. - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES

  • General Photograph - BROKEN PIPE

    79.6 ft. - General Photograph - BROKEN PIPE

  • General Observation - CHIPPING

    162.3 ft. - General Observation - CHIPPING

  • Joint Offset Medium

    187.8 ft. - Joint Offset Medium

  • Joint Separated Medium

    187.9 ft. - Joint Separated Medium

Observations (32)

DistanceCodeObservation
49.7CM
44.9FL
246.4AMH1:23 PM
38.4JSM
146.9CL
0MGOROACHES INSIDE THE MH.
105.6CL
0AMH12:52 PM
162.3MGOCHIPPING
187.9JSM
100.6CM
90.3CL
245.1MGOROACHES INSIDE THE MH.
48.7CL
23FMPOSSIBLY BROKEN
79.6B
95.3CM
79.6MGPBROKEN PIPE
187.8JOM
226.2TFC
244.9MGOSAGS THROUGHOUT THE REACH
38.4JOL
43.9FL
48.7FCPOSSIBLY BROKEN
44.4TFC
240CM
48.6FL
48.7JSM
0MWL
244.9MGOSLIGHT GREASE THROUGHOUT THE REACH
0MWM
59.1CM

Properties (7)

additional_info
RFIR INSPECTION
custom_field_three
BROKEN PIPE
custom_field_two
1
customer
LACSD
datetime
2016-08-23T12:49:42-07:00
documentation
MIRANDA, FRANKLIN, SHADLER, BRAR
is_lateral_inspection
false