Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 21, 2016, 03:09 PM
  • 19 0039_19 0038_8212016_081541.mp4

Date
08/21/2016
W/O
0585475
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00725
PipeID
P15069
Time
8:09 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7211
Sewer Name
19 FULLERTON ROAD TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary
District
District 19
Page No.
09
Purpose
Routine Assessment
Project
20160821AM_FULLERTON_ROAD_TRUNK
Material
Vitrified Clay Pipe
Shape
Other
Height
12 in.
Upstream MH
19 0039
Downstream MH
19 0038
Dir. of Survey
Downstream
Length Surveyed
276.9 ft.
Total Length
276.9 ft.
Structural Index
2
Structural Quick
4338
Structural Rating
54
O&M Index
2
O&M Quick
2B00
O&M Rating
28
Overall Index
2
Overall Quick
Overall Rating
82
Pipe schematic from manhole 19 0039 to 19 0038
MH: 19 0039MH: 19 0038downstream0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 8:15 AM0 ft. MWM - Water Mark, 25 %of cross sectional area8.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: YES14.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: YES24.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES25.1 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES35.8 ft. MGO - General Observation - CHIPPING37.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"38.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES38.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN43.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES43.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES48.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES53.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 10 to 11 o'clock, , within 8 inches of joint: YES53.4 ft. MWL - Water Level, 25 %of cross sectional area63.8 ft. CC - Crack Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES63.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 01 to 04 o'clock, , within 8 inches of joint: YES79.3 ft. CM - Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES90.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"107.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 11 to 12 o'clock, , within 8 inches of joint: YES112.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: YES113.4 ft. CC - Crack Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES117.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 02 o'clock, , within 8 inches of joint: YES117.4 ft. CC - Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES139.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"140.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES140.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES145.7 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES150.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES150.6 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES155.7 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES155.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start161.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES166.2 ft. CM - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES176 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES186.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES187.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"199.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES204.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES214.4 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES220 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES234.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start241 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"269.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"270.4 ft. FM - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN270.4 ft. JSM - Joint Separated Medium275.6 ft. MGO - General Observation - SLIGHT GREASE/CALCIUM THROUGHOUT THE REACH275.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish275.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish276.1 ft. MGO - General Observation - ROACHES INSIDE THE MH.276.9 ft. AMH - Downstream Manhole, Survey Ends - 9:00 AM

Observation photos (9)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 12 o'clock,  , within 8 inches of joint: YES

    8.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 10 o'clock,  , within 8 inches of joint: YES

    14.6 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    38.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Water Level, 25 %of cross sectional area

    53.4 ft. - Water Level, 25 %of cross sectional area

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 12 o'clock,  , within 8 inches of joint: YES

    112.7 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    140.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    199.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    270.4 ft. - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Joint Separated Medium

    270.4 ft. - Joint Separated Medium

Observations (53)

DistanceCodeObservation
107.8DAE
79.3CM
25.1CM
234.8CM
43.5CM
214.4CM
117.4DAE
113.4CC
161.1CL
0MGOROACHES INSIDE THE MH.
0MWL
220CL
150.5DAE
8.1DAE
204.2CL
63.8CC
145.7CL
166.2CM
150.6CL
0AMH8:15 AM
186.6CM
43.5DAE
176CL
38.2DAE
155.7CL
276.1MGOROACHES INSIDE THE MH.
275.6MGOSLIGHT GREASE/CALCIUM THROUGHOUT THE REACH
24.9DAE
199.6CM
270.4FMPOSSIBLY BROKEN
0MWM
155.7DAE
241TFC
63.8DAE
14.6DAE
140.7DAE
187.6TFC
53.4DAE
140.7FM
38.2FMPOSSIBLY BROKEN
275.6CM
37.2TFC
48.9DAE
90.6TFC
35.8MGOCHIPPING
276.9AMH9:00 AM
53.4MWL
270.4JSM
275.6DAE
117.4CC
269.4TFC
112.7DAE
139.5TFC

Properties (6)

custom_field_three
POSSIBLE BROKEN PIPE
custom_field_two
1
customer
LACSD
datetime
2016-08-21T08:09:24-07:00
documentation
MIRANDA & FRANKLIN
is_lateral_inspection
false