Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 19, 2016, 06:52 AM
  • H 0257_H 0256_8182016_005905.mp4

Date
08/18/2016
W/O
0
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00171
PipeID
P10679
Time
11:52 PM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0243
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
VERNON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Maintenance Related
Project
20160818MDM_JOINT_OUTFALL_H_UNIT_2F
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
H 0256
Downstream MH
H 0255
Dir. of Survey
Downstream
Length Surveyed
393.4 ft.
Total Length
393.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole H 0256 to H 0255
MH: H 0256MH: H 0255downstream0 ft. MWL - Water Level, 5 %of cross sectional area - NO FLOW0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:40AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active1 ft. MGO - General Observation - POST GREASE CCTV92.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped99.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped147.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES160.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open168.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped235.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped235.2 ft. MGO - General Observation - 21" VCP251.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped310 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped316.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open393.4 ft. AMH - Downstream Manhole, Survey Ends - 1:00AM

Observation photos (1)

  • General Observation - 21" VCP

    235.2 ft. - General Observation - 21" VCP

Observations (16)

DistanceCodeObservation
0MWLNO FLOW
0MWM
310TFCCapped
168.8TFCCapped
251.7TFCCapped
316.9TFOpen
1MGOPOST GREASE CCTV
0AMH12:40AM
160.8TFOpen
0MGOConn. @ Mh, 3 O' Clock. Active
92.2TFCCapped
393.4AMH1:00AM
99.7TFCCapped
235.2TFCCapped
147.4DAGS
235.2MGO21" VCP

Properties (5)

additional_info
POST GREASE CCTV
customer
LACSD
datetime
2016-08-18T23:52:44-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false