Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2016, 10:23 AM
  • 08 0468_08 0467_8132016_062851.mp4

Date
08/13/2016
W/O
0585838
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00524
Time
3:23 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0236
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20160813MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0468
Downstream MH
08 0467
Dir. of Survey
Downstream
Length Surveyed
442.9 ft.
Total Length
442.9 ft.
Structural Index
5
Structural Quick
5841
Structural Rating
44
O&M Index
5
O&M Quick
5200
O&M Rating
10
Overall Index
5
Overall Quick
Overall Rating
54
Pipe schematic from manhole 08 0468 to 08 0467
MH: 08 0468MH: 08 0467downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 6:20AM0 ft. MWM - Water Mark, 85 %of cross sectional area0 ft. MWL - Water Level, 60 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS MISSING TILES2 ft. MGO - General Observation - MISSING TILES 30% START 9:00 TO 3:00 START4.1 ft. DSZ - Deposits Settled Other, 50 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES - MISSING TILES14 ft. MGO - General Observation - 100% MISSING TILES START14 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED & MISSING AREAS MISSING TILES14 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR AREAS MISSING TILES16.8 ft. MGP - General Photograph23.3 ft. MGO - General Observation - MISSING TILES 20% START53.5 ft. MGO - General Observation - 50% MISSING TILES START662 ft. MGO - General Observation - 100% MISSING TILES START73.8 ft. MGO - General Observation - MISSING TILES 30% START89 ft. MGO - General Observation - 100% MISSING TILES START101 ft. MGO - General Observation - 40 % MISSING TILES111.7 ft. SRC - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR133.8 ft. MGO - General Observation - 100% MISSING TILES START147.2 ft. MGO - General Observation - MISSING TILES 10%162.2 ft. MGO - General Observation - 30% MISSING TILES START179.4 ft. MGO - General Observation - 100% MISSING TILES195.7 ft. MGO - General Observation - 100% MISSING TILES223.7 ft. MGO - General Observation - 100 % MISSING TILES230.8 ft. MGO - General Observation - 100% MISSING TILES240.4 ft. MGO - General Observation - 40% MISSING TILES START240.4 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BROKEN REBAR CIRCUM242.9 ft. MGP - General Photograph243.5 ft. MGO - General Observation - CORRISON BEYOUND REBAR TOP OF PIPE291.1 ft. MGO - General Observation - 100% MSSING TILES START291.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - MISSING REBAR-CORRISON BEYOUND REBAR302.9 ft. MGO - General Observation - 30% MISSING TILES START314.8 ft. MGO - General Observation - 100% MISSING TILES START319.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR- CORRISON BEYOUND REBAR331.8 ft. MGO - General Observation - 40% MISSING TILES START355.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR CORRISON BEYOUND REBAR363.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - MISSING REBAR CORRISON BEYOUND REBAR363.2 ft. MGO - General Observation - 100% MISSING TILES START371 ft. MGP - General Photograph384.9 ft. MGP - General Photograph388.3 ft. MGP - General Photograph407.5 ft. MGP - General Photograph442.6 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG442.6 ft. MGO - General Observation - MISSING TILES 100% FINISH442.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CORRODED BEYOUND REBAR442.6 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Finish - LONG REBAR442.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN442.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CORRODED MISSING CIRCUM REBAR442.9 ft. AMH - Downstream Manhole, Survey Ends - 7:50AM

Observation photos (33)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS MISSING TILES

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS MISSING TILES

  • General Observation - MISSING TILES 30% START 9:00 TO 3:00 START

    2 ft. - General Observation - MISSING TILES 30% START 9:00 TO 3:00 START

  • Deposits Settled Other,  50 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES - MISSING TILES

    4.1 ft. - Deposits Settled Other, 50 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES - MISSING TILES

  • General Observation - 100% MISSING TILES START

    14 ft. - General Observation - 100% MISSING TILES START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED & MISSING AREAS MISSING TILES

    14 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED & MISSING AREAS MISSING TILES

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR AREAS MISSING TILES

    14 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR AREAS MISSING TILES

  • General Photograph

    16.8 ft. - General Photograph

  • General Observation - MISSING TILES 20% START

    23.3 ft. - General Observation - MISSING TILES 20% START

  • General Observation - 50% MISSING TILES START6

    53.5 ft. - General Observation - 50% MISSING TILES START6

  • General Observation - 100% MISSING TILES START

    62 ft. - General Observation - 100% MISSING TILES START

  • General Observation - MISSING TILES 30% START

    73.8 ft. - General Observation - MISSING TILES 30% START

  • General Observation - 100% MISSING TILES START

    89 ft. - General Observation - 100% MISSING TILES START

  • Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    111.7 ft. - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Observation - 30% MISSING TILES START

    162.2 ft. - General Observation - 30% MISSING TILES START

  • General Observation - 100% MISSING TILES

    179.4 ft. - General Observation - 100% MISSING TILES

  • General Observation - 100% MISSING TILES

    195.7 ft. - General Observation - 100% MISSING TILES

  • General Observation - 100   % MISSING TILES

    223.7 ft. - General Observation - 100 % MISSING TILES

  • General Observation - 100% MISSING TILES

    230.8 ft. - General Observation - 100% MISSING TILES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BROKEN REBAR CIRCUM

    240.4 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED BROKEN REBAR CIRCUM

  • General Photograph

    242.9 ft. - General Photograph

  • General Observation - CORRISON BEYOUND REBAR TOP OF PIPE

    243.5 ft. - General Observation - CORRISON BEYOUND REBAR TOP OF PIPE

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - MISSING REBAR-CORRISON BEYOUND REBAR

    291.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - MISSING REBAR-CORRISON BEYOUND REBAR

  • General Observation - 30% MISSING TILES START

    302.9 ft. - General Observation - 30% MISSING TILES START

  • General Observation - 100% MISSING TILES START

    314.8 ft. - General Observation - 100% MISSING TILES START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR- CORRISON BEYOUND REBAR

    319.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR- CORRISON BEYOUND REBAR

  • General Observation - 40% MISSING TILES START

    331.8 ft. - General Observation - 40% MISSING TILES START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR CORRISON BEYOUND REBAR

    355.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR CORRISON BEYOUND REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - MISSING REBAR CORRISON BEYOUND REBAR

    363.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - MISSING REBAR CORRISON BEYOUND REBAR

  • General Observation - 100% MISSING TILES START

    363.2 ft. - General Observation - 100% MISSING TILES START

  • General Photograph

    371 ft. - General Photograph

  • General Photograph

    384.9 ft. - General Photograph

  • General Photograph

    388.3 ft. - General Photograph

  • General Photograph

    407.5 ft. - General Photograph

Observations (49)

DistanceCodeObservation
371MGP
384.9MGP
442.6SAMSEVERE AGG
89MGO100% MISSING TILES START
101MGO40 % MISSING TILES
319.5SRCBROKEN REBAR- CORRISON BEYOUND REBAR
2SAMSEVERE AGG AREAS MISSING TILES
407.5MGP
291.1MGO100% MSSING TILES START
240.4MGO40% MISSING TILES START
16.8MGP
442.6MGOMISSING TILES 100% FINISH
355.6SRCMISSING REBAR CORRISON BEYOUND REBAR
111.7SRCCIRCUM REBAR
4.1DSZMISSING TILES
0MGOConn. @ Mh, 3 O' Clock. OPEN
23.3MGOMISSING TILES 20% START
291.1SRCMISSING REBAR-CORRISON BEYOUND REBAR
147.2MGOMISSING TILES 10%
302.9MGO30% MISSING TILES START
53.5MGO50% MISSING TILES START6
14MGO100% MISSING TILES START
179.4MGO100% MISSING TILES
14SRCCIRCUM REBAR CORRODED & MISSING AREAS MISSING TILES
73.8MGOMISSING TILES 30% START
442.6SRCCORRODED BEYOUND REBAR
240.4SRCCORRODED BROKEN REBAR CIRCUM
133.8MGO100% MISSING TILES START
0AMH6:20AM
230.8MGO100% MISSING TILES
14SRCLONG REBAR AREAS MISSING TILES
363.2SRCMISSING REBAR CORRISON BEYOUND REBAR
442.9AMH7:50AM
62MGO100% MISSING TILES START
442.6SRCLONG REBAR
162.2MGO30% MISSING TILES START
0MWM
388.3MGP
243.5MGOCORRISON BEYOUND REBAR TOP OF PIPE
442.6MGOConn. @ Mh, 3 O' Clock. OPEN
363.2MGO100% MISSING TILES START
331.8MGO40% MISSING TILES START
223.7MGO100 % MISSING TILES
195.7MGO100% MISSING TILES
314.8MGO100% MISSING TILES START
0MWL
442.6SRCCORRODED MISSING CIRCUM REBAR
242.9MGP
2MGOMISSING TILES 30% START 9:00 TO 3:00 START

Properties (6)

custom_field_three
MISSING REBAR CORRISON BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2016-08-13T03:23:53-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false