Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2016, 05:33 PM
  • H 0343_H 0342_6242016_104605.mp4

Date
06/24/2016
W/O
0580931
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00175
PipeID
P10793
Time
10:33 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7159
Sewer Name
H JOINT OUTFALL H - UNIT 4
City
PICO RIVERA
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
06
Purpose
Routine Assessment
Project
20160624_JOINT_OUTFALL_H_UNIT_4
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
H 0342
Downstream MH
H 0343
Dir. of Survey
Upstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
4
Structural Quick
5231
Structural Rating
15
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole H 0342 to H 0343
MH: H 0342MH: H 0343upstream0 ft. AMH - Downstream Manhole, Survey Ends - ABLE TO SEE MH. H 3430.1 ft. SRC - Surface Reinforcement Corroded, at 11 o'clock, within 8 inches of joint: NO0.1 ft. MGO - General Observation - 50% MAG COAT FROM 08 TO 04 O'CLOCK0.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO0.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO0.1 ft. MGO - General Observation - CORRODED PIPE, POSSIBLE MISSING WALL0.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO2.1 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK2.1 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. AMH - Downstream Manhole, Survey Begins - 10:43 AM

Observation photos (9)

  • General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK

    0 ft. - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK

  • Water Level, 15 %of cross sectional area

    0 ft. - Water Level, 15 %of cross sectional area

  • Downstream Manhole, Survey Begins - 10:43 AM

    0 ft. - Downstream Manhole, Survey Begins - 10:43 AM

  • Surface Reinforcement Corroded, at 11 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Reinforcement Corroded, at 11 o'clock, within 8 inches of joint: NO

  • General Observation - 50% MAG COAT FROM 08 TO 04 O'CLOCK

    2 ft. - General Observation - 50% MAG COAT FROM 08 TO 04 O'CLOCK

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO

  • Downstream Manhole, Survey Ends - ABLE TO SEE MH. H 343

    2.1 ft. - Downstream Manhole, Survey Ends - ABLE TO SEE MH. H 343

Observations (10)

DistanceCodeObservation
2SRC
2MGO50% MAG COAT FROM 08 TO 04 O'CLOCK
2SSS
2.1AMHABLE TO SEE MH. H 343
2SAV
2MGOCORRODED PIPE, POSSIBLE MISSING WALL
0MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
2SRV
0MWL
0AMH10:43 AM

Properties (7)

additional_info
JUST GOING TO HANG THE CAMERA IN THE CENTER OF THE MH. AND ZOOM IN U/S TOWARDS MH. H 343
custom_field_three
REBAR, POSSIBLE MISSING WALL
custom_field_two
1
customer
LACSD
datetime
2016-06-24T10:33:19-07:00
documentation
MIRANDA, IGNACIO, SHADLER
is_lateral_inspection
false