Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2016, 09:02 AM
  • A 0324_A 0323_6242016_035250.mp4

Date
06/24/2016
W/O
0574318
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00325
PipeID
P08234
Time
2:02 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0168
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20160624MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Upstream MH
A 0324
Downstream MH
A 0323
Dir. of Survey
Downstream
Length Surveyed
8.7 ft.
Total Length
8.7 ft.
Structural Index
5
Structural Quick
5941
Structural Rating
49
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
49
Pipe schematic from manhole A 0324 to A 0323
MH: A 0324MH: A 0323downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:55AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area1 ft. MGO - General Observation - TOP OF PIPE TO SURFACE 8'4"2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES - CIRCUM & LONG REBAR2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG4.1 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"4.1 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"4.1 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"4.1 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"4.1 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"4.1 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"4.1 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"8.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish8.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish8.7 ft. MSA - Survey Abandoned - DOWNLEG UPSTREAM SIPHON

Observation photos (12)

  • Water Level, 15 %of cross sectional area

    0 ft. - Water Level, 15 %of cross sectional area

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES - CIRCUM & LONG REBAR

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES - CIRCUM & LONG REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

    4.1 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

    4.1 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

    4.1 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

    4.1 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

    4.1 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE  24" X 40"

    4.1 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

    4.1 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES - SOIL VISIBLE 24" X 40"

  • Survey Abandoned - DOWNLEG UPSTREAM SIPHON

    8.7 ft. - Survey Abandoned - DOWNLEG UPSTREAM SIPHON

Observations (17)

DistanceCodeObservation
2SRCCIRCUM & LONG REBAR
4.1SMWSOIL VISIBLE 24" X 40"
4.1SMWSOIL VISIBLE 24" X 40"
8.1SAM
0AMH3:55AM
4.1SMWSOIL VISIBLE 24" X 40"
1MGOTOP OF PIPE TO SURFACE 8'4"
2SRCCIRCUM & LONG REBAR
4.1SMWSOIL VISIBLE 24" X 40"
4.1SMWSOIL VISIBLE 24" X 40"
4.1SMWSOIL VISIBLE 24" X 40"
0MWM
4.1SMWSOIL VISIBLE 24" X 40"
8.1SRC
8.7MSADOWNLEG UPSTREAM SIPHON
0MWL
2SAMSEVERE AGG

Properties (7)

additional_info
DOWNLEG UPSTREAM SIPHON
custom_field_three
MISSING WALL SOIL VISIBLE
custom_field_two
1
customer
LACSD
datetime
2016-06-24T02:02:34-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false