Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2016, 08:09 AM
  • A 0328_A 0327_6242016_011710.mp4

Date
06/24/2016
W/O
0574318
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00325
PipeID
P08238
Time
1:09 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0168
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20160624MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Upstream MH
A 0328
Downstream MH
A 0327
Dir. of Survey
Downstream
Length Surveyed
3 ft.
Total Length
3 ft.
Structural Index
5
Structural Quick
5241
Structural Rating
14
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
19
Pipe schematic from manhole A 0328 to A 0327
MH: A 0328MH: A 0327downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:10AM0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. MWL - Water Level, 60 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM3 ft. MSA - Survey Abandoned - DOWNLEG UPSTREAM SIPHON

Observation photos (5)

  • Water Mark, 80 %of cross sectional area

    0 ft. - Water Mark, 80 %of cross sectional area

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • Survey Abandoned - DOWNLEG UPSTREAM SIPHON

    3 ft. - Survey Abandoned - DOWNLEG UPSTREAM SIPHON

Observations (7)

DistanceCodeObservation
2SRVCIRCUM
0AMH1:10AM
0MWM
2SAMSEVERE AGG
3MSADOWNLEG UPSTREAM SIPHON
0MWL
2SRVCIRCUM

Properties (7)

additional_info
DOWNLEG UPSTREAM SIPHON
custom_field_three
CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2016-06-24T01:09:29-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false