- Date
- 06/27/2016
- W/O
- 0563388
- Weather
- Very Dry
- Operator/Surveyor
- MIRANDA
- Sewer ID
- Z00347
- PipeID
- P10443
- Time
- 9:30 AM
- Certificate
- U-1014-06022542
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G7161
- Sewer Name
- G JOINT OUTFALL G - UNIT 7
- City
- COMPTON
- Loc. details
- Other
- Location Code
- Z
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 05
- Purpose
- Routine Assessment
- Project
- 20160623AM_JOINT_OUTFALL_G_UNIT_7
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 36 in.
- Upstream MH
- G 0081
- Downstream MH
- G 0080
- Dir. of Survey
- Downstream
- Length Surveyed
- 592.4 ft.
- Total Length
- 592.4 ft.
- Structural Index
- 3
- Structural Quick
- 3121
- Structural Rating
- 5
- O&M Index
- 4
- O&M Quick
- 4100
- O&M Rating
- 4
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 9
Pipe schematic from manhole G 0081 to G 0080 Observation photos (6)

0 ft. - Upstream Manhole, Survey Begins - 10:20 AM

2 ft. - General Observation - 80% MAG COAT FROM 08 TO 04 O'CLOCK, START

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

388.7 ft. - Water Level, 40 %of cross sectional area

496.8 ft. - Water Level, 20 %of cross sectional area