Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2016, 08:13 AM
  • A 0376_A 0375_6212016_013643.mp4

Date
06/21/2016
W/O
0574368
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00325
PipeID
P08286
Time
1:13 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
HO160
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
15
Purpose
Capital Improvement Program Assesment
Project
20160621MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
A 0376
Downstream MH
A 0375
Dir. of Survey
Downstream
Length Surveyed
378.6 ft.
Total Length
378.6 ft.
Structural Index
2
Structural Quick
3223
Structural Rating
12
O&M Index
4
O&M Quick
4200
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole A 0376 to A 0375
MH: A 0376MH: A 0375downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:15AM2 ft. MGO - General Observation - MAG COAT 70% START 9:00 TO 3:002 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE38.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE38.9 ft. MGO - General Observation - MAG COAT 50% START47.7 ft. MWM - Water Mark, 60 %of cross sectional area78.3 ft. SAV - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG84.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE378.1 ft. MGO - General Observation - MAG COAT 50% FINISH378.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE378.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC378.6 ft. AMH - Downstream Manhole, Survey Ends - 1:55AM

Observation photos (6)

  • General Observation - MAG COAT 70% START 9:00 TO 3:00

    2 ft. - General Observation - MAG COAT 70% START 9:00 TO 3:00

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    38.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG

    78.3 ft. - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    84.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

Observations (15)

DistanceCodeObservation
0MWL
378.1MGOMAG COAT 50% FINISH
0MWM
2MGOMAG COAT 70% START 9:00 TO 3:00
47.7MWM
38.9SSSBLISTERING PEELING CONCRETE
84.2SSSPEELING CONCRETE
38.9MGOMAG COAT 50% START
378.1SSSBLISTERING PEELING CONCRETE
378.1SAVSEVERE AGG SPORATIC
2SAVSEVERE AGG SPORATIC
78.3SAVSEVERE AGG
378.6AMH1:55AM
0AMH1:15AM
2SSSBLISTERING PEELING CONCRETE

Properties (7)

custom_field_three
SEVERE AGG SPORATIC 50% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2016-06-21T01:13:16-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false
year_laid
19800829