Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2016, 10:02 AM
Date
06/17/2016
W/O
0577470
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01125
PipeID
P13536
Time
3:02 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6719
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
16
Purpose
Routine Assessment
Project
20160617MDM_JOINT_OUTFALL_B_UNIT_6H
Material
Vitrified Clay Pipe
Shape
Circular
Height
20 in.
Upstream MH
B 1157
Downstream MH
B 1156
Dir. of Survey
Downstream
Length Surveyed
44.6 ft.
Total Length
44.6 ft.
Structural Index
3
Structural Quick
3722
Structural Rating
25
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
25
Pipe schematic from manhole B 1157 to B 1156
MH: B 1157MH: B 1156downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:35AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - MH 9:00 ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MMC - Material Change, Vitrified clay pipe6.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE7.9 ft. MGO - General Observation - 20" VCP18.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE26.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE26.4 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE28.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE34.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE36.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H39.1 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES - H41.9 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H44.2 ft. MMC - Material Change, Vitrified clay pipe, Finish - LINE IS VCP NOT NRCP44.2 ft. MGP - General Photograph - BRICK LINE DOWNSTREAM44.6 ft. AMH - Downstream Manhole, Survey Ends - 3:55AM

Observation photos (5)

  • Material Change, Vitrified clay pipe

    2 ft. - Material Change, Vitrified clay pipe

  • General Observation - 20" VCP

    7.9 ft. - General Observation - 20" VCP

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    18.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    28.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • General Photograph - BRICK LINE DOWNSTREAM

    44.2 ft. - General Photograph - BRICK LINE DOWNSTREAM

Observations (18)

DistanceCodeObservation
2MMC
44.2MMCLINE IS VCP NOT NRCP
0AMH3:35AM
7.9MGO20" VCP
41.9FCH
44.6AMH3:55AM
34.5FLHAIRLINE
18.5FLHAIRLINE
0MWM
0MGOMH 9:00 ACTIVE
44.2MGPBRICK LINE DOWNSTREAM
6.5FLHAIRLINE
28.8FLHAIRLINE
26.4FLHAIRLINE
26.4FCHAIRLINE
0MWL
39.1FLH
36.4FLH

Properties (7)

additional_info
PIPE IS VCP NOT NRCP
custom_field_three
HAIRLINE FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2016-06-17T03:02:45-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false