Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 13, 2016, 08:50 AM
  • A 0386_A 0387_6132016_023158.mp4

Date
06/13/2016
W/O
0577469
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00325
PipeID
P08296
Time
1:50 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0159
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20160611MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
A 0386
Downstream MH
A 0385
Dir. of Survey
Downstream
Length Surveyed
343.5 ft.
Total Length
343.5 ft.
Structural Index
3
Structural Quick
5234
Structural Rating
24
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole A 0386 to A 0385
MH: A 0386MH: A 0385downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:10AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING PEELING CONCRETE10.4 ft. MGO - General Observation - MAG COAT 70% 8:00 TO 4:0015.1 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC34.8 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR44.8 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG102.5 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC184.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR POSSIBLE224.5 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC343 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC343 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SWOLLEN BLISTERING PEELING CONCETE343.5 ft. AMH - Downstream Manhole, Survey Ends - 2:50AM

Observation photos (8)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING PEELING CONCRETE

  • General Observation - MAG COAT 70% 8:00 TO 4:00

    10.4 ft. - General Observation - MAG COAT 70% 8:00 TO 4:00

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    15.1 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    34.8 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    44.8 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    102.5 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR POSSIBLE

    184.3 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR POSSIBLE

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    224.5 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

Observations (14)

DistanceCodeObservation
0AMH2:10AM
15.1SAVSEVERE AGG SPORATIC
343.5AMH2:50AM
184.3SRVCIRCUM REBAR POSSIBLE
102.5SAVSEVERE AGG SPORATIC
0MWM
10.4MGOMAG COAT 70% 8:00 TO 4:00
2SSSSWOLLEN BLISTERING PEELING CONCRETE
34.8SRVCIRCUM REBAR
0MWL
343SAVSEVERE AGG SPORATIC
44.8SAVSEVERE AGG
224.5SAVSEVERE AGG SPORATIC
343SSSSWOLLEN BLISTERING PEELING CONCETE

Properties (6)

custom_field_three
CIRCUM RBAR -SEVERE AGG-70% MAG COAT
custom_field_two
2
customer
LACSD
datetime
2016-06-13T01:50:36-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false