Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2016, 05:53 PM
  • 05 2216_05 1263_6152016_110425.mp4

Date
06/15/2016
W/O
0574349
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00518
PipeID
P06475
Time
10:53 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
06/15/16
Pre-Cleaning
Jetting
Media Label
G7151
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
20160609AM_SO_HAWTHORNE_WARFIELD_AV_EXT_TR_SECT_4
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 1263
Downstream MH
05 2216
Dir. of Survey
Upstream
Length Surveyed
271.1 ft.
Total Length
271.1 ft.
Structural Index
3
Structural Quick
3421
Structural Rating
14
O&M Index
2
O&M Quick
3123
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
23
Pipe schematic from manhole 05 1263 to 05 2216
MH: 05 1263MH: 05 2216upstream0 ft. MSA - Survey Abandoned - INSPECTION COMPLETED ON A REVERSE PULL0.3 ft. RML - Roots Medium Lateral, from 07 to 11 o'clock, 45 %, within 8 inches of joint: NO - TAP ROOTS COMING OUT OF THE CONN.1.8 ft. MGO - General Observation - SLIGHT GREASE/DEBRIS THROUGHOUT THE REACH1.8 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish83.6 ft. DAZ - Deposits Attached Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES85.8 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 4"96.7 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS148.1 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 4"197.3 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - CAPPED, BROKEN201.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"248.5 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start252.8 ft. CM - Crack Multiple, from 09 to 05 o'clock, within 8 inches of joint: YES256.5 ft. CM - Crack Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES260.6 ft. CM - Crack Multiple, from 07 to 04 o'clock, within 8 inches of joint: YES264 ft. CS - Crack Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES, Finish - ENDS AS A FRACTURE268.1 ft. CS - Crack Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES, Start271.1 ft. MWL - Water Level, 5 %of cross sectional area - STAGNANT WATER271.1 ft. AMH - Downstream Manhole, Survey Begins - 11:01 AM271.1 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK271.1 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (9)

  • Crack Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Crack Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES, Finish - ENDS AS A FRACTURE

    7.1 ft. - Crack Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES, Finish - ENDS AS A FRACTURE

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    22.6 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - CAPPED, BROKEN

    73.8 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - CAPPED, BROKEN

  • Deposits Attached Other, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES - DEBRIS

    174.4 ft. - Deposits Attached Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS

  • Deposits Attached Other, 10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES

    187.5 ft. - Deposits Attached Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish

    269.3 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish

  • Roots Medium Lateral, from 07 to 11 o'clock, 45 %, within 8 inches of joint: NO - TAP ROOTS COMING OUT OF THE CONN.

    270.8 ft. - Roots Medium Lateral, from 07 to 11 o'clock, 45 %, within 8 inches of joint: NO - TAP ROOTS COMING OUT OF THE CONN.

  • Survey Abandoned - INSPECTION COMPLETED ON A REVERSE PULL

    271.1 ft. - Survey Abandoned - INSPECTION COMPLETED ON A REVERSE PULL

Observations (20)

DistanceCodeObservation
0MWLSTAGNANT WATER
269.3MGOSLIGHT GREASE/DEBRIS THROUGHOUT THE REACH
0AMH11:01 AM
22.6CM
123TBA
269.3CM
0MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
174.4DAZDEBRIS
10.5CM
187.5DAZ
0MWM
14.6CM
271.1MSAINSPECTION COMPLETED ON A REVERSE PULL
7.1CSENDS AS A FRACTURE
18.3CM
270.8RMLTAP ROOTS COMING OUT OF THE CONN.
73.8TFDCAPPED, BROKEN
185.3TBA
69.9TFA
3CS

Properties (5)

additional_info
NEED TO CCTV APPROX. 268' U/S TO COMPLETE INSPECTION ON A REVERSE PULL
customer
LACSD
datetime
2016-06-15T10:53:36-07:00
documentation
MIRANDA, SHADLER, FRANKLIN
is_lateral_inspection
false