Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 14, 2016, 04:01 PM
  • 05 1270_05 1269_6142016_090459.mp4

Date
06/14/2016
W/O
0574349
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00518
PipeID
P06482
Time
9:01 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7149
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
20160609AM_SO_HAWTHORNE_WARFIELD_AV_EXT_TR_SECT_4
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 1270
Downstream MH
05 1269
Dir. of Survey
Downstream
Length Surveyed
342.5 ft.
Total Length
342.5 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
33
O&M Index
2
O&M Quick
2600
O&M Rating
12
Overall Index
3
Overall Quick
Overall Rating
45
Pipe schematic from manhole 05 1270 to 05 1269
MH: 05 1270MH: 05 1269downstream0 ft. AMH - Upstream Manhole, Survey Begins - 9:03 AM0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK0 ft. MGO - General Observation - CAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area14.4 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES18.8 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES23.1 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES31.1 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES35.2 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES55.2 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES59.1 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES63.1 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES64.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - CRACKED, STUFFED WITH DEBRIS67.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start80.7 ft. MGP - General Photograph - BLOCKAGE INSIDE THE PROTRUDING CONN.80.7 ft. TFI - Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 2" - UNKNOWN, 100% BLOCKAGE153.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"174 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN180 ft. MGO - General Observation - CHIPPING192.1 ft. RTJ - Roots Tap Joint, from 11 to 12 o'clock, 5 %, within 8 inches of joint: YESR212.4 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES225.7 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN, 90% BLOCKED229.7 ft. MGP - General Photograph - 95% ROOT BLOCKAGE INSIDE THE CONN.229.7 ft. TFI - Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 2" - OPEN, 95% BLOCKAGE261.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"268.4 ft. MGP - General Photograph - CHIPPING290 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - CAPPED, CRACKED304.8 ft. JSM - Joint Separated Medium340.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish340.9 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH341.1 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK342.5 ft. AMH - Downstream Manhole, Survey Ends - 9:47 AM

Observation photos (11)

  • Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

    35.2 ft. - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - CRACKED, STUFFED WITH DEBRIS

    64.6 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - CRACKED, STUFFED WITH DEBRIS

  • General Photograph - BLOCKAGE INSIDE THE PROTRUDING CONN.

    80.7 ft. - General Photograph - BLOCKAGE INSIDE THE PROTRUDING CONN.

  • Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 2" - UNKNOWN, 100% BLOCKAGE

    80.7 ft. - Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 2" - UNKNOWN, 100% BLOCKAGE

  • General Observation - CHIPPING

    180 ft. - General Observation - CHIPPING

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    212.4 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN, 90% BLOCKED

    225.7 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - UNKNOWN, 90% BLOCKED

  • General Photograph - 95% ROOT BLOCKAGE INSIDE THE CONN.

    229.7 ft. - General Photograph - 95% ROOT BLOCKAGE INSIDE THE CONN.

  • Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 2" - OPEN, 95% BLOCKAGE

    229.7 ft. - Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 2" - OPEN, 95% BLOCKAGE

  • General Photograph - CHIPPING

    268.4 ft. - General Photograph - CHIPPING

  • Joint Separated Medium

    304.8 ft. - Joint Separated Medium

Observations (33)

DistanceCodeObservation
80.7MGPBLOCKAGE INSIDE THE PROTRUDING CONN.
63.1CM
59.1CM
340.9CM
341.1MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
55.2CM
0AMH9:03 AM
0MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
0MGOCAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK
261.8TFC
229.7MGP95% ROOT BLOCKAGE INSIDE THE CONN.
174TBOPEN
14.4CL
67.2CM
340.9MGOSLIGHT GREASE THROUGHOUT THE REACH
290TFDCAPPED, CRACKED
268.4MGPCHIPPING
0MWM
229.7TFIOPEN, 95% BLOCKAGE
31.1CM
64.6TFDCRACKED, STUFFED WITH DEBRIS
192.1RTJ
180MGOCHIPPING
212.4FM
304.8JSM
35.2B
0MWL
80.7TFIUNKNOWN, 100% BLOCKAGE
225.7TFDUNKNOWN, 90% BLOCKED
153.3TFC
23.1CM
18.8CM
342.5AMH9:47 AM

Properties (6)

custom_field_three
BROKEN PIPE
custom_field_two
1
customer
LACSD
datetime
2016-06-14T09:01:21-07:00
documentation
MIRANDA, SHADLER, IGNACIO
is_lateral_inspection
false