Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 13, 2016, 05:34 PM
  • 05 1271_05 1270_6132016_103737.mp4

Date
06/13/2016
W/O
0574349
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00518
PipeID
P06483
Time
10:34 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7148
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
20160609AM_SO_HAWTHORNE_WARFIELD_AV_EXT_TR_SECT_4
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 1270
Downstream MH
05 1271
Dir. of Survey
Upstream
Length Surveyed
93.7 ft.
Total Length
93.7 ft.
Structural Index
4
Structural Quick
5241
Structural Rating
28
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
34
Pipe schematic from manhole 05 1270 to 05 1271
MH: 05 1270MH: 05 1271upstream0 ft. TFI - Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2" - UNKNOWN, PVC PIPE PROTRUDING IN OUR LINE0 ft. MSA - Survey Abandoned - INSPECTION COMPLETED ON A REVERSE PULL, PVC PIPE BLOCKING THE LINE0 ft. MGO - General Observation - MULTIPLE CRACKS/FRACTURES THROUGHOUT THE REACH0 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH0.3 ft. MGP - General Photograph - PVC PIPE BROKEN AT THE END5 ft. MGO - General Observation - PVC PIPE PROTRUDING IN OUR LINE14 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES18.1 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES19.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"26.1 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES42.4 ft. B - Broken, from 10 to 03 o'clock, within 8 inches of joint: YES50.3 ft. FM - Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES66.6 ft. FC - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN78.9 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES83.3 ft. B - Broken, from 10 to 03 o'clock, within 8 inches of joint: YES93.7 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK93.7 ft. MWM - Water Mark, 50 %of cross sectional area93.7 ft. AMH - Downstream Manhole, Survey Begins - 10:36 AM93.7 ft. MGO - General Observation - CAPPED CONN. INSIDE THE MH. @ 09 O'CLOCK93.7 ft. MWL - Water Level, 35 %of cross sectional area

Observation photos (8)

  • Broken, from 10 to 03 o'clock, within 8 inches of joint: YES

    10.4 ft. - Broken, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    27.1 ft. - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

    43.4 ft. - Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Broken, from 10 to 03 o'clock, within 8 inches of joint: YES

    51.3 ft. - Broken, from 10 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - PVC PIPE PROTRUDING IN OUR LINE

    88.7 ft. - General Observation - PVC PIPE PROTRUDING IN OUR LINE

  • General Photograph - PVC PIPE BROKEN AT THE END

    93.4 ft. - General Photograph - PVC PIPE BROKEN AT THE END

  • Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2" - UNKNOWN, PVC PIPE PROTRUDING IN OUR LINE

    93.7 ft. - Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2" - UNKNOWN, PVC PIPE PROTRUDING IN OUR LINE

  • Survey Abandoned - INSPECTION COMPLETED ON A REVERSE PULL, PVC PIPE BLOCKING THE LINE

    93.7 ft. - Survey Abandoned - INSPECTION COMPLETED ON A REVERSE PULL, PVC PIPE BLOCKING THE LINE

Observations (20)

DistanceCodeObservation
0MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
88.7MGOPVC PIPE PROTRUDING IN OUR LINE
93.7TFIUNKNOWN, PVC PIPE PROTRUDING IN OUR LINE
67.6CM
93.7MSAINSPECTION COMPLETED ON A REVERSE PULL, PVC PIPE BLOCKING THE LINE
93.4MGPPVC PIPE BROKEN AT THE END
43.4FM
14.8CM
0MWM
51.3B
0AMH10:36 AM
10.4B
27.1FCPOSSIBLY BROKEN
74.3TFC
75.6CM
0MGOCAPPED CONN. INSIDE THE MH. @ 09 O'CLOCK
0MWL
93.7MGOMULTIPLE CRACKS/FRACTURES THROUGHOUT THE REACH
93.7MGOSLIGHT GREASE THROUGHOUT THE REACH
79.7CM

Properties (7)

additional_info
JUST GOING TO CCTV APPROX 90' U/S TO COMPLETE INSPECTION ON A REVERSE PULL
custom_field_three
BROKEN PIPE, PVC PIPE PROTRUDING INSIDE OUR PIPE
custom_field_two
1
customer
LACSD
datetime
2016-06-13T10:34:43-07:00
documentation
MIRANDA, FRANKLIN, SHADLER
is_lateral_inspection
false