- Date
- 06/08/2016
- W/O
- 0568722
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00635
- PipeID
- P12054
- Time
- 1:10 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0153
- Sewer Name
- 15 TYLER AVENUE RELIEF TRUNK
- City
- EL MONTE
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 23
- Purpose
- Routine Assessment
- Project
- 20160606MDM_TYLER_AVENUE_RELIEF_TRUNK
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- 15 0153
- Downstream MH
- 15 0152
- Dir. of Survey
- Downstream
- Length Surveyed
- 680.6 ft.
- Total Length
- 680.6 ft.
- Structural Index
- 2
- Structural Quick
- 3224
- Structural Rating
- 14
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 14
Pipe schematic from manhole 15 0153 to 15 0152 Observation photos (6)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING LAITANCE COAT

8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - LAITANCE COAT

44.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING LATANCE COAT

268.5 ft. - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - SEVERE AGG

413.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - LAITANCE COAT PEELING

631.7 ft. - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC