Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2016, 08:52 AM
  • 18 0037_18 0036_642016_034525.mp4

Date
06/04/2016
W/O
0563300
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00689
PipeID
P13852
Time
1:52 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0149
Sewer Name
18 MILLS AVENUE TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
20160604MDM_MILLS_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
18 0037
Downstream MH
18 0036
Dir. of Survey
Downstream
Length Surveyed
307.9 ft.
Total Length
307.9 ft.
Structural Index
2
Structural Quick
3124
Structural Rating
11
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 18 0037 to 18 0036
MH: 18 0037MH: 18 0036downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:30AM0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 30% START 8:00 TO 4:002 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE & LAITANCE COAT4.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE40.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active51.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped57.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped81.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE105.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped112.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped145.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO157.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped163.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped208.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped214.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open271.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped278.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped280.3 ft. MWM - Water Mark, 50 %of cross sectional area280.3 ft. MGO - General Observation - MAG COAT 5% START307.5 ft. MGO - General Observation - Conn. @ Mh, 2 O' Clock. Active307.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active307.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG307.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONRETE & LAITANCE COAT307.5 ft. MGO - General Observation - MAG COAT 5% FINISH307.9 ft. AMH - Downstream Manhole, Survey Ends - 4:00AM

Observation photos (6)

  • General Observation - MAG COAT 30% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 30% START 8:00 TO 4:00

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE & LAITANCE COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE & LAITANCE COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    4.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE

    81.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO

    145.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO

Observations (28)

DistanceCodeObservation
307.5MGOConn. @ Mh, 2 O' Clock. Active
0MWL
307.5MGOConn. @ Mh, 3 O' Clock. Active
157.2TFCCapped
280.3MWM
2MGOMAG COAT 30% START 8:00 TO 4:00
307.5SAVSEVERE AGG
208.3TFCCapped
81.3SSSBLISTERING CONCRETE
214.8TFOpen
271.9TFCCapped
105.6TFCCapped
163.2TFCCapped
278.6TFCCapped
145.8SSS
280.3MGOMAG COAT 5% START
2SAVSEVERE AGG
307.5SSSBLISTERING PEELING CONRETE & LAITANCE COAT
0AMH3:30AM
307.9AMH4:00AM
112.2TFCCapped
0MWM
40.2TBActive
57.3TFCCapped
307.5MGOMAG COAT 5% FINISH
51.5TFCCapped
2SSSPEELING BLISTERING CONCRETE & LAITANCE COAT
4.5SSSPEELING CONCRETE

Properties (6)

custom_field_three
SEVERE AGG VISIBLE -CONCREE SPALLING
custom_field_two
2
customer
LACSD
datetime
2016-06-04T01:52:48-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false