Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2016, 12:50 PM
  • 15 0370_15 0369_642016_070409.mp4

Date
06/04/2016
W/O
0563341
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00598
PipeID
P12296
Time
5:50 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0150
Sewer Name
15 BALDWIN PARK TRUNK
City
BALDWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
18
Purpose
Routine Assessment
Project
20160604MDM_BALDWIN_PARK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
15 0369
Downstream MH
15 0370
Dir. of Survey
Upstream
Length Surveyed
303.9 ft.
Total Length
303.9 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 15 0369 to 15 0370
MH: 15 0369MH: 15 0370upstream0 ft. AMH - Downstream Manhole, Survey Ends - 7:35AM0.3 ft. MGO - General Observation - Conn. @ Mh, 2 O' Clock. Active0.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active51.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG51.3 ft. MWM - Water Mark, 60 %of cross sectional area106.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active196.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG301.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG302.9 ft. MMC - Material Change, Concrete pipe (non-reinfored) - PIPE IS NOT VCP303.9 ft. AMH - Upstream Manhole, Survey Begins - 7:15AM303.9 ft. MWL - Water Level, 30 %of cross sectional area303.9 ft. MWM - Water Mark, 30 %of cross sectional area303.9 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active

Observation photos (4)

  • Material Change, Concrete pipe (non-reinfored) - PIPE IS NOT VCP

    1 ft. - Material Change, Concrete pipe (non-reinfored) - PIPE IS NOT VCP

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    107.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

    252.6 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

Observations (14)

DistanceCodeObservation
303.6MGOConn. @ Mh, 2 O' Clock. Active
0AMH7:15AM
0MWL
252.6SAVSEVERE AGG
107.7SAVSEVERE AGG
303.6SAVSEVERE AGG
303.9AMH7:35AM
2SAVSEVERE AGG
197.8TBActive
1MMCPIPE IS NOT VCP
303.6MGOConn. @ Mh, 3 O' Clock. Active
252.6MWM
0MWM
0MGOConn. @ Mh, 3 O' Clock. Active

Properties (6)

custom_field_three
SEVERE AGG VISIBLE
custom_field_two
3
customer
LACSD
datetime
2016-06-04T05:50:09-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false