Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2016, 03:20 PM
  • H 0089_H 0088_622016_090719.mp4

Date
06/02/2016
W/O
0576775
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00165
PipeID
P10541
Time
8:20 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7139
Sewer Name
H JOINT OUTFALL H - UNIT 1F
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Maintenance Related
Project
20160602AM_JOINT_OUTFALL_H_UNIT_1F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
H 0089
Downstream MH
H 0088
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole H 0089 to H 0088
MH: H 0089MH: H 0088downstream0 ft. MWL - Water Level, 100 %of cross sectional area0 ft. MGO - General Observation - AIRLINE0 ft. AMH - Upstream Manhole, Survey Begins - 9:05 AM2 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO2 ft. SMW - Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: NO - VOID WITH SOIL VISIBLE2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO2.1 ft. MSA - Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

Observation photos (7)

  • Water Level, 100 %of cross sectional area

    0 ft. - Water Level, 100 %of cross sectional area

  • General Observation - AIRLINE

    0 ft. - General Observation - AIRLINE

  • Upstream Manhole, Survey Begins - 9:05 AM

    0 ft. - Upstream Manhole, Survey Begins - 9:05 AM

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: NO - VOID WITH SOIL VISIBLE

    2 ft. - Surface Missing Wall, from 11 to 01 o'clock, within 8 inches of joint: NO - VOID WITH SOIL VISIBLE

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

    2.1 ft. - Survey Abandoned - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

Observations (7)

DistanceCodeObservation
2.1MSAVIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
2SAV
0MWL
2SMWVOID WITH SOIL VISIBLE
0MGOAIRLINE
2SSS
0AMH9:05 AM

Properties (7)

additional_info
VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
custom_field_three
VOID WITH SOIL VISIBLE
custom_field_two
1
customer
LACSD
datetime
2016-06-02T08:20:55-07:00
documentation
MIRANDA, SHADLER, FRANKLIN
is_lateral_inspection
false