Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 31, 2016, 03:58 PM
  • 30 0088_30 0087_5312016_090135.mp4

Date
05/31/2016
W/O
0568757
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00878
PipeID
P17796
Time
8:58 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7136
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
05
Purpose
Routine Assessment
Project
20160528AM_SOUTH_BAY_CITIES_MAIN_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
30 0088
Downstream MH
30 0087
Dir. of Survey
Downstream
Length Surveyed
80.8 ft.
Total Length
80.8 ft.
Structural Index
3
Structural Quick
3421
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
14
Pipe schematic from manhole 30 0088 to 30 0087
MH: 30 0088MH: 30 0087downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - OPEN CONN. INSIDE THE MH. @ 09 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 9:00 AM19.4 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES28.7 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES32 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES35 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES37.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start77.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish79.7 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 07 O'CLOCK80.8 ft. AMH - Downstream Manhole, Survey Ends - 9:16 AM

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    35 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    37.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWL
0MWM
77.5CM
79.7MGOACTIVE CONN. INSIDE THE MH. @ 07 O'CLOCK
35CM
19.4CM
37.8CM
80.8AMH9:16 AM
32CL
0MGOOPEN CONN. INSIDE THE MH. @ 09 O'CLOCK
28.7CM
0AMH9:00 AM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2016-05-31T08:58:57-07:00
documentation
MIRANDA, SHADLER, IGNACIO
is_lateral_inspection
false