Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 28, 2016, 03:14 PM
  • 30 0086_18 0085_5282016_081648.mp4

Date
05/28/2016
W/O
0568757
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00878
PipeID
P17794
Time
8:14 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7134
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
05
Purpose
Routine Assessment
Project
20160528AM_SOUTH_BAY_CITIES_MAIN_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
18 0085
Downstream MH
30 0086
Dir. of Survey
Upstream
Length Surveyed
26.5 ft.
Total Length
26.5 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0085 to 30 0086
MH: 18 0085MH: 30 0086upstream0 ft. AMH - Upstream Manhole, Survey Ends - 8:22 AM, PRESSURE PLATE1.5 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH21.4 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES21.4 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES26.5 ft. MWL - Water Level, 20 %of cross sectional area26.5 ft. MWM - Water Mark, 30 %of cross sectional area26.5 ft. AMH - Downstream Manhole, Survey Begins - 8:16 AM

Observation photos (3)

  • Downstream Manhole, Survey Begins - 8:16 AM

    0 ft. - Downstream Manhole, Survey Begins - 8:16 AM

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    5.1 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES

    5.1 ft. - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
0MWL
25MGOSLIGHT GREASE THROUGHOUT THE REACH
0MWM
0AMH8:16 AM
5.1CL
5.1CC
26.5AMH8:22 AM, PRESSURE PLATE

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2016-05-28T08:14:52-07:00
documentation
MIRANDA, FRANKLIN, SHADLER
is_lateral_inspection
false