Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 23, 2016, 03:40 PM
  • 18 0284_18 0283_5232016_084512.mp4

Date
05/23/2016
W/O
0568850
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00702
PipeID
P14112
Time
8:40 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7128
Sewer Name
18 SHOEMAKER AVENUE TRUNK
City
NORWALK
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
20160523AM_SHOEMAKER_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
18 0284
Downstream MH
18 0283
Dir. of Survey
Downstream
Length Surveyed
333 ft.
Total Length
333 ft.
Structural Index
3
Structural Quick
3321
Structural Rating
11
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 18 0284 to 18 0283
MH: 18 0284MH: 18 0283downstream0 ft. AMH - Upstream Manhole, Survey Begins - 8:43 AM0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - ROACHES INSIDE THE MH.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start2 ft. MGO - General Observation - 90% MAG COAT FROM 09 TO 03 O'CLOCK, START27.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - UNKNOWN30.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - UNKNOWN32.2 ft. MWLS - Water Level, Sag in pipe, 45 %of cross sectional area, Start76.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"79.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"86.3 ft. MWLS - Water Level, Sag in pipe, 45 %of cross sectional area, Finish124 ft. MWLS - Water Level, Sag in pipe, 45 %of cross sectional area, Start125.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"128.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"171.9 ft. MWLS - Water Level, Sag in pipe, 45 %of cross sectional area, Finish180.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - UNKNOWN183.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - UNKNOWN229.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"232.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"280.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"284 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"331 ft. MGO - General Observation - SAGS THROUGHOUT THE REACH331.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish331.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish331.1 ft. MGO - General Observation - 90% MAG COAT FROM 09 TO 03 O'CLOCK, FINISH331.7 ft. MGO - General Observation - ROACHES INSIDE THE MH.331.7 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK331.7 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK333 ft. AMH - Downstream Manhole, Survey Ends - 9:15 AM

Observation photos (10)

  • Water Level, 35 %of cross sectional area

    0 ft. - Water Level, 35 %of cross sectional area

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • General Observation - 90% MAG COAT FROM 09 TO 03 O'CLOCK, START

    2 ft. - General Observation - 90% MAG COAT FROM 09 TO 03 O'CLOCK, START

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - UNKNOWN

    27.7 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - UNKNOWN

  • Water Level, Sag in pipe, 45 %of cross sectional area, Start

    32.2 ft. - Water Level, Sag in pipe, 45 %of cross sectional area, Start

  • Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    76.9 ft. - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"

    79.9 ft. - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"

  • Water Level, Sag in pipe, 45 %of cross sectional area, Finish

    86.3 ft. - Water Level, Sag in pipe, 45 %of cross sectional area, Finish

  • Water Level, Sag in pipe, 45 %of cross sectional area, Start

    124 ft. - Water Level, Sag in pipe, 45 %of cross sectional area, Start

Observations (31)

DistanceCodeObservation
0AMH8:43 AM
180.7TFUNKNOWN
2SAV
333AMH9:15 AM
331MGOSAGS THROUGHOUT THE REACH
229.3TFC
171.9MWLS
284TFC
79.9TFC
232.4TFC
125.7TFC
27.7TFUNKNOWN
331.7MGOROACHES INSIDE THE MH.
124MWLS
331.1SAV
0MWL
86.3MWLS
0MWM
183.6TFUNKNOWN
76.9TFC
30.5TFUNKNOWN
331.1SSS
331.1MGO90% MAG COAT FROM 09 TO 03 O'CLOCK, FINISH
331.7MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
128.8TFC
2SSS
32.2MWLS
2MGO90% MAG COAT FROM 09 TO 03 O'CLOCK, START
0MGOROACHES INSIDE THE MH.
331.7MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
280.9TFC