Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2016, 01:15 PM
  • 15 0376_15 0375_5212016_064326.mp4

Date
05/21/2016
W/O
0563341
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00598
PipeID
P12302
Time
6:15 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7127
Sewer Name
15 BALDWIN PARK TRUNK
City
BALDWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
18
Purpose
Routine Assessment
Project
20160521AM_BALDWIN_PARK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
15 0376
Downstream MH
15 0375
Dir. of Survey
Downstream
Length Surveyed
338.5 ft.
Total Length
338.5 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 15 0376 to 15 0375
MH: 15 0376MH: 15 0375downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. MGO - General Observation - CAPPED CONN. INSIDE THE MH. @ 09 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 6:41 AM2 ft. MMC - Material Change, Other (state in comments) - CONCRETE PIPE2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start32.7 ft. MWLS - Water Level, Sag in pipe, 35 %of cross sectional area, Start39.9 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 6" - OPEN65.9 ft. MWLS - Water Level, Sag in pipe, 35 %of cross sectional area, Finish73.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN166.9 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 60% BLOCKED224.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4" - OPEN, POSSIBLE BREAK-IN227.3 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 6"268.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"277.7 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 4" - OPEN280.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN326 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN336.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish336.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish336.8 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK336.8 ft. MGO - General Observation - ROACHES INSIDE THE MH.338.5 ft. AMH - Downstream Manhole, Survey Ends - 7:08 AM

Observation photos (6)

  • Water Level, 20 %of cross sectional area

    0 ft. - Water Level, 20 %of cross sectional area

  • Material Change, Other (state in comments) - CONCRETE PIPE

    2 ft. - Material Change, Other (state in comments) - CONCRETE PIPE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Water Level, Sag in pipe, 35 %of cross sectional area, Start

    32.7 ft. - Water Level, Sag in pipe, 35 %of cross sectional area, Start

  • Water Level, Sag in pipe, 35 %of cross sectional area, Finish

    65.9 ft. - Water Level, Sag in pipe, 35 %of cross sectional area, Finish

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 60% BLOCKED

    166.9 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, 60% BLOCKED

Observations (25)

DistanceCodeObservation
32.7MWLS
336.3SAV
2MMCCONCRETE PIPE
227.3TFA
326TBOPEN
2SAV
2SSS
65.9MWLS
336.8MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
277.7TBOPEN
0MWM
268.7TFA
280.4TFOPEN
338.5AMH7:08 AM
0MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
224.5TFOPEN, POSSIBLE BREAK-IN
0MGOROACHES INSIDE THE MH.
39.9TFOPEN
336.3SSS
73.4TFOPEN
166.9TFDOPEN, 60% BLOCKED
0MGOCAPPED CONN. INSIDE THE MH. @ 09 O'CLOCK
336.8MGOROACHES INSIDE THE MH.
0MWL
0AMH6:41 AM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2016-05-21T06:15:46-07:00
documentation
MIRANDA & FRANKLIN
is_lateral_inspection
false