Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2016, 07:35 PM
  • C 0173_C 0172_5182016_131209.mp4

Date
05/18/2016
W/O
0568717
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00130
PipeID
P09697
Time
12:35 PM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7124
Sewer Name
C JOINT OUTFALL C - UNIT 5C
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
10
Purpose
Routine Assessment
Project
20160517AM_JOINT_OUTFALL_C_UNIT_5C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0173
Downstream MH
C 0172
Dir. of Survey
Downstream
Length Surveyed
254.2 ft.
Total Length
254.2 ft.
Structural Index
5
Structural Quick
5B31
Structural Rating
75
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
5
Overall Quick
Overall Rating
77
Pipe schematic from manhole C 0173 to C 0172
MH: C 0173MH: C 0172downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:10 PM0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start40.9 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO, Start42.5 ft. SRC - Surface Reinforcement Corroded, from 01 to 02 o'clock, within 8 inches of joint: NO45.3 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO, Finish62.4 ft. SRV - Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO77.6 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO85.2 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO89.6 ft. SRV - Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO, Start94.5 ft. SRV - Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO, Finish121.1 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO121.8 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO124.4 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO143.1 ft. TBI - Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: NO, 4", 2" - ACTIVE177 ft. SRV - Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO196.2 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: YES205.7 ft. SRV - Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO237.3 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO245.8 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO, Start249.6 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO, Finish252.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish252.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish252.4 ft. MGO - General Observation - ROACHES INSIDE THE MH.252.4 ft. MGO - General Observation - CAPPED CONN. INSIDE THE MH. @ 09 O'CLOCK252.4 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK254.2 ft. AMH - Downstream Manhole, Survey Ends - 1:39 PM

Observations (32)

DistanceCodeObservation
85.2SRV
121.8SRV
94.5SRV
252.4MGOROACHES INSIDE THE MH.
252.3SSS
121.1SRV
0AMH1:10 PM
196.2SRV
0MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
124.4SRV
40.9SRV
2SAV
252.4MGOCAPPED CONN. INSIDE THE MH. @ 09 O'CLOCK
89.6SRV
2SSS
0MWM
252.4MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
177SRV
0MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
237.3SRV
143.1TBIACTIVE
77.6SRV
245.8SRV
205.7SRV
45.3SRV
0MGOROACHES INSIDE THE MH.
252.3SAV
254.2AMH1:39 PM
249.6SRV
42.5SRC
0MWL
62.4SRV

Properties (7)

additional_info
COULD NOT TAKE PICS, COMPUTER PROBLEMS
custom_field_three
REBAR
custom_field_two
2
customer
LACSD
datetime
2016-05-18T12:35:23-07:00
documentation
MIRANDA, SHADLER, FRANKLIN
is_lateral_inspection
false