Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 16, 2016, 03:30 PM
  • C 0313_C 0312A_5162016_083924.mp4

Date
05/16/2016
W/O
0563383
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00135
PipeID
P09775
Time
8:30 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7119
Sewer Name
C JOINT OUTFALL C - UNIT 6F
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
20160516AM_JOINT_OUTFALL_C_UNIT_6F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Upstream MH
C 0312A
Downstream MH
C 0313
Dir. of Survey
Upstream
Length Surveyed
206.4 ft.
Total Length
206.4 ft.
Structural Index
4
Structural Quick
5431
Structural Rating
25
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
25
Pipe schematic from manhole C 0312A to C 0313
MH: C 0312AMH: C 0313upstream0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish0.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish0.7 ft. MGO - General Observation - GREASE/CALCIUM INSIDE THE MH.110.9 ft. SRV - Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO181.9 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES198.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish204.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start204.4 ft. SRV - Surface Reinforcement Visible, from 11 to 03 o'clock, within 8 inches of joint: YES, Start204.4 ft. MGP - General Photograph - REBAR204.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start206.4 ft. MGO - General Observation - ROACHES INSIDE THE MH.206.4 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK206.4 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK206.4 ft. MWL - Water Level, 20 %of cross sectional area206.4 ft. MWM - Water Mark, 30 %of cross sectional area206.4 ft. AMH - Downstream Manhole, Survey Begins - 8:40 AM206.4 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

Observation photos (10)

  • Water Level, 20 %of cross sectional area

    0 ft. - Water Level, 20 %of cross sectional area

  • Water Mark, 30 %of cross sectional area

    0 ft. - Water Mark, 30 %of cross sectional area

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

    0 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 11 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 11 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - REBAR

    2 ft. - General Photograph - REBAR

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    8.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

  • Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO

    95.5 ft. - Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO

  • General Observation - GREASE/CALCIUM INSIDE THE MH.

    205.7 ft. - General Observation - GREASE/CALCIUM INSIDE THE MH.

Observations (18)

DistanceCodeObservation
2SSS
205.7SAV
0MGOROACHES INSIDE THE MH.
0MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
206.4MGOROACHES INSIDE THE MH.
0MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
0MWL
24.5SRV
2SRV
205.7SSS
0MWM
8.1SRV
2MGPREBAR
205.7MGOGREASE/CALCIUM INSIDE THE MH.
0AMH8:40 AM
2SAV
95.5SRV
0SRV

Properties (6)

custom_field_three
REBAR
custom_field_two
2
customer
LACSD
datetime
2016-05-16T08:30:15-07:00
documentation
MIRANDA, FRANKLIN, SHADLER
is_lateral_inspection
false