Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 16, 2016, 08:10 AM
  • C 0299_C 0298_5162016_022718.mp4

  • C 0299_C 0298_5162016_022837.mp4

Date
05/16/2016
W/O
0563393
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00134
PipeID
P09759
Time
1:10 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H 0133
Sewer Name
C JOINT OUTFALL C - UNIT 6E
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
20160514MDM_JOINT_OUTFALL_C_UNIT_6E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0298
Downstream MH
C 0299
Dir. of Survey
Upstream
Length Surveyed
719.9 ft.
Total Length
719.9 ft.
Structural Index
3
Structural Quick
3624
Structural Rating
26
O&M Index
2
O&M Quick
382H
O&M Rating
114
Overall Index
2
Overall Quick
Overall Rating
140
Pipe schematic from manhole C 0298 to C 0299
MH: C 0298MH: C 0299upstream0 ft. AMH - Upstream Manhole, Survey Ends - 3:15AM0.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING BLISTERING CONCRETE0.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG VERY SPORATIC0.3 ft. MGO - General Observation - MAG COAT FINISH20.9 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped20.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 03 o'clock, , within 8 inches of joint: NO29 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Capped29 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 10 o'clock, , within 8 inches of joint: NO - Capped42.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 01 to 03 o'clock, , within 8 inches of joint: YES77.3 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Peeling & Flaking Throughout The Reach85.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 10 o'clock, , within 8 inches of joint: NO85.4 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Capped120.6 ft. SAV - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO125.9 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped133.9 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: NO133.9 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Capped174.6 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped182.8 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Capped223 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped230.8 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Capped236 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES237.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 11 o'clock, , within 8 inches of joint: YES239 ft. SAV - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO244.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES244.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 12 o'clock, , within 8 inches of joint: YES268.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 03 o'clock, , within 8 inches of joint: YES279.4 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped287.4 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES287.6 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Capped293.4 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES301.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 11 o'clock, , within 8 inches of joint: YES317.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES325.1 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 12 to 03 o'clock, , within 8 inches of joint: YES328.3 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped334.4 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 12 to 03 o'clock, , within 8 inches of joint: YES336.5 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Capped352.9 ft. MGO - General Observation - ABANDONED MH364 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped371.9 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Capped385.7 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES393.1 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES393.1 ft. ID - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES404.3 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped412.1 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Capped418.6 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 11 o'clock, , within 8 inches of joint: YES444.5 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped452.9 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Capped490 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 12 to 04 o'clock, , within 8 inches of joint: YES493.4 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped501.2 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped550.1 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped555.8 ft. SAV - Surface Aggregate Visible, from 12 to 01 o'clock, within 8 inches of joint: NO590.4 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped598.6 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped619.2 ft. SAV - Surface Aggregate Visible, from 10 to 11 o'clock, within 8 inches of joint: NO639.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES647.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 10 o'clock, , within 8 inches of joint: YES647.1 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped649.1 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES653.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 12 o'clock, , within 8 inches of joint: YES653.4 ft. MGO - General Observation - ABANDONED MH655.1 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped663.4 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC688.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG VERY SPORATIC695.2 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped704 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: NO704 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Capped717.9 ft. MGO - General Observation - MAG COAT 20% 9:00 TO 3:00 START717.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: NO - AROUND PIPE OPENING717.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE719.9 ft. MWL - Water Level, 20 %of cross sectional area719.9 ft. MWM - Water Mark, 40 %of cross sectional area719.9 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active719.9 ft. AMH - Downstream Manhole, Survey Begins - 1:55AM

Observation photos (24)

  • General Observation - MAG COAT 20% 9:00 TO 3:00 START

    2 ft. - General Observation - MAG COAT 20% 9:00 TO 3:00 START

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: NO - AROUND PIPE OPENING

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: NO - AROUND PIPE OPENING

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 02 to 04 o'clock,  , within 8 inches of joint: NO

    15.9 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: NO

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG VERY SPORATIC

    31.4 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG VERY SPORATIC

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC

    56.5 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC

  • General Observation - ABANDONED MH

    66.5 ft. - General Observation - ABANDONED MH

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES

    70.8 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

    80.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

    100.7 ft. - Surface Aggregate Visible, from 10 to 11 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Visible, from 12 to 01 o'clock, within 8 inches of joint: NO

    164.1 ft. - Surface Aggregate Visible, from 12 to 01 o'clock, within 8 inches of joint: NO

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 12 to 04 o'clock,  , within 8 inches of joint: YES

    229.9 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 12 to 04 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES

    326.8 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES

    334.2 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES

  • General Observation - ABANDONED MH

    367 ft. - General Observation - ABANDONED MH

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 12 to 03 o'clock,  , within 8 inches of joint: YES

    385.5 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 12 to 03 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 12 to 03 o'clock,  , within 8 inches of joint: YES

    394.8 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 12 to 03 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES

    426.5 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES

    432.5 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

    475 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

    480.9 ft. - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

    483.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 10 o'clock,  , within 8 inches of joint: NO

    586 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: NO

  • Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO

    599.3 ft. - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO

Observations (74)

DistanceCodeObservation
599.3SAV
2MGOMAG COAT 20% 9:00 TO 3:00 START
451.2DAE
301.3DAE
496.9TBCCapped
70.8DAE
307.8TBCCapped
326.8DAE
719.6SSSPEELING BLISTERING CONCRETE
24.7TBCCapped
121.3TBCCapped
594TBCCapped
426.5DAE
367MGOABANDONED MH
634.5DAE
56.5SAVSEVERE AGG VERY SPORATIC
315.6TBCCapped
348TBCCapped
15.9DAE
475SSS
267TBCCapped
489.1TBCCapped
677.6DAE
440.5TBCCapped
482.8DAE
432.5DAE
355.9TBCCapped
2DAEAROUND PIPE OPENING
690.9TBCCapped
432.3TBCCapped
586DAE
2SSSPEELING BLISTERING CONCRETE
719.6SAVSEVERE AGG VERY SPORATIC
418.8DAE
402.7DAE
66.5DAE
0MWL
66.5MGOABANDONED MH
0MWM
719.6MGOMAG COAT FINISH
0MGOConn. @ Mh, 3 O' Clock. Active
699TBCCapped
169.8TBCCapped
642.6TBCPeeling & Flaking Throughout The Reach
72.8DAE
385.5DAE
31.4SAVSEVERE AGG VERY SPORATIC
586TBCCapped
218.7TBCCapped
537.1TBCCapped
64.8TBCCapped
383.4TBCCapped
480.9SAV
229.9DAE
275.4TBCCapped
690.9DAECapped
475DAE
334.2DAE
394.8DAE
719.9AMH3:15AM
326.8ID
0AMH1:55AM
483.9SSS
15.9TBCCapped
545.3TBCCapped
699DAE
391.6TBCCapped
634.5TBCCapped
164.1SAV
100.7SAV
72.8TBCCapped
80.1SSS
226.5TBCCapped
129.5TBCCapped

Properties (6)

custom_field_three
SEVERE AGG VERY SPORATIC
custom_field_two
3
customer
LACSD
datetime
2016-05-16T01:10:34-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false