Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2016, 08:09 AM
  • 01 0019A_01 0019_5102016_034838.mp4

Date
05/10/2016
W/O
0563420
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00209
PipeID
P00769
Time
1:09 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0125
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Capital Improvement Program Assesment
Project
201605MDM_HOOPER_AVENUE_COMPTON_CREEK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Upstream MH
01 0019A
Downstream MH
01 0019
Dir. of Survey
Downstream
Length Surveyed
380.9 ft.
Total Length
380.9 ft.
Structural Index
3
Structural Quick
3E2C
Structural Rating
128
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
130
Pipe schematic from manhole 01 0019A to 01 0019
MH: 01 0019AMH: 01 0019downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:50AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 5 %of cross sectional area8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT11.9 ft. MGO - General Observation - 27" VCP14.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE19.3 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - HAIRLINE26.7 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE27.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish27.2 ft. FS - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT31.6 ft. FS - Fracture Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE31.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT32.4 ft. FS - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Finish35.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE39.8 ft. FS - Fracture Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT39.8 ft. FS - Fracture Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES, Finish43.9 ft. FS - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT46.8 ft. MGP - General Photograph46.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT52.6 ft. FS - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Finish - SLIGHT55 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT55 ft. FS - Fracture Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT71.2 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE74.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE74.9 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE78.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT78.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE106.4 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SLIGHT106.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE106.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT106.4 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SLIGHT108.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE118.8 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE124.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT130.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start130.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H141.3 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT141.3 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H154.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish173.1 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT173.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, - H181.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H184.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H186.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H189.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H189.5 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT195.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish201.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H217.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish221 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H225.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H228.8 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H244.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Change - H256.1 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H260.1 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H263.9 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H267.8 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - H271.4 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H282.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H282.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT284 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT291.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H322.9 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - H338.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H338.9 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H349.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H358.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish373.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H380.4 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active380.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active380.9 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (14)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    27.2 ft. - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    31.6 ft. - Fracture Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    39.8 ft. - Fracture Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    43.9 ft. - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • General Photograph

    46.8 ft. - General Photograph

  • Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Finish - SLIGHT

    52.6 ft. - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Finish - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    55 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    71.2 ft. - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    78.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    106.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    130.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES,  - H

    173.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, - H

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Change - H

    244.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Change - H

Observations (72)

DistanceCodeObservation
221FCH
11.9MGO27" VCP
154.4DAGS
338.9FLH
55FLSLIGHT
181.4FLH
71.2FSHAIRLINE
322.9FCH
271.4FLH
106.4FCSLIGHT
349.9FLH
74.9FLHAIRLINE
184.9FLH
27.2FL
43.9FSSLIGHT
35.1FLHAIRLINE
380.4MGOConn. @ Mh, 9 O' Clock. Active
189.5FLH
26.7FCHAIRLINE
46.8MGP
201.3FLH
263.9FCH
46.8FCSLIGHT
228.8FCH
284FLSLIGHT
39.8FSSLIGHT
124.9FLSLIGHT
0MWM
282.3FCH
380.9AMH5:00AM
244.5FLH
373.9FLH
19.3FLHAIRLINE
217.9FL
260.1FLH
118.8FCHAIRLINE
291.6FCH
195.8FL
256.1FLH
106.4FLHAIRLINE
27.2FSSLIGHT
39.8FS
8FLSLIGHT
32.4FS
31.6FSHAIRLINE
52.6FSSLIGHT
358.4FL
173.1FLSLIGHT
0AMH3:50AM
225.3FCH
106.4FLSLIGHT
173.1FLH
130.3DAGS
130.3FLH
14.8FLHAIRLINE
141.3FCSLIGHT
141.3FCH
282.3FCSLIGHT
186.7FCH
0MGOConn. @ Mh, 3 O' Clock. Active
189.5FCSLIGHT
106.4FCSLIGHT
55FSSLIGHT
78.7FLSLIGHT
338.9FLH
108.4FCHAIRLINE
78.7FLHAIRLINE
0MWL
74.9FSHAIRLINE
380.4MGOConn. @ Mh, 3 O' Clock. Active
31.6FLSLIGHT
267.8FCH

Properties (6)

custom_field_three
SLIGHT FRACTURES JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2016-05-10T01:09:42-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false