C 0315_C 0314_592016_092914.mp4
0 ft. - Water Level, 20 %of cross sectional area
0 ft. - General Observation - ROACHES INSIDE THE MH.
0 ft. - Upstream Manhole, Survey Begins - 9:28 AM
0 ft. - Water Mark, 30 %of cross sectional area
2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start
2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start
35.3 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES
36.7 ft. - Surface Reinforcement Visible, from 11 to 02 o'clock, within 8 inches of joint: YES, Start
38.9 ft. - General Photograph - REBAR
43.8 ft. - Surface Reinforcement Visible, from 11 to 02 o'clock, within 8 inches of joint: YES, Finish
46.8 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES, Start
49.4 ft. - General Observation - REBAR
51.7 ft. - Tap Break-In Defective, at 03 o'clock, -, , within 8 inches of joint: YES, 6" - ACTIVE, CRACKED
52.8 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES, Finish
62.5 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES, Start
63.9 ft. - General Photograph - REBAR/CORROSION
69.2 ft. - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES, Finish
109.2 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO
173.8 ft. - Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO
179.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES
181.4 ft. - Surface Reinforcement Visible, from 12 to 04 o'clock, within 8 inches of joint: YES
190.3 ft. - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO
194.4 ft. - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES
195.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start
209.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES
209.5 ft. - Surface Reinforcement Visible, at 09 o'clock, within 8 inches of joint: YES, Start
248.8 ft. - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO, Start
252.6 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: YES
262.8 ft. - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO, Finish
285.9 ft. - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES
297.9 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO, Start
302.2 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO
314.1 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES
314.6 ft. - Survey Abandoned - CALCIUM DEPOSITS
| Distance | Code | Observation |
|---|---|---|
| 173.8 | SRV | — |
| 285.9 | SRV | — |
| 297.9 | SRV | — |
| 157 | TFA | — |
| 2 | SSS | — |
| 46.8 | SRV | — |
| 181.4 | SRV | — |
| 248.8 | SRV | — |
| 109.2 | SRV | — |
| 52.8 | SRV | — |
| 202.3 | SRV | — |
| 49.4 | MGO | REBAR |
| 194.4 | SRV | — |
| 2 | SAV | — |
| 107 | TB | OPEN |
| 314.1 | TF | OPEN |
| 62.5 | SRV | — |
| 35.3 | SRV | — |
| 0 | MWL | — |
| 0 | MGO | ROACHES INSIDE THE MH. |
| 179.4 | SAV | — |
| 314.1 | MGO | CORRODED PIPE THROUGHOUT THE REACH |
| 0 | AMH | 9:28 AM |
| 212.5 | SRV | — |
| 69.2 | SRV | — |
| 195.7 | SRV | — |
| 209.3 | SAV | — |
| 314.1 | DAE | — |
| 302.2 | SRV | — |
| 36.7 | SRV | — |
| 209.5 | SRV | — |
| 38.9 | MGP | REBAR |
| 302.2 | SRV | — |
| 314.1 | SAV | — |
| 252.6 | SRV | — |
| 63.9 | MGP | REBAR/CORROSION |
| 43.8 | SRV | — |
| 262.8 | SRV | — |
| 51.7 | TBD | ACTIVE, CRACKED |
| 314.6 | MSA | CALCIUM DEPOSITS |
| 190.3 | SRV | — |
| 0 | MWM | — |
| 314.1 | SSS | — |