Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2017, 10:17 AM
  • B 1126_B 1125_06072017_031811.mp4

Date
07/06/2017
W/O
640678
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13166
Time
3:17 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4635
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
ALHAMBRA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
23
Purpose
Routine Assessment
Project
WO_640678_TV16072_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
22 in.
Width
22 in.
Upstream MH
B 1126
Downstream MH
B 1125
Dir. of Survey
Downstream
Length Surveyed
270.6 ft.
Total Length
270.7 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
156
Pipe schematic from manhole B 1126 to B 1125
MH: B 1126MH: B 1125downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 11260 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area4.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start65.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"72.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"84.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"87.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"169.2 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"184.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"204.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"216.6 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"219.8 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"264.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"266.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish270.7 ft. AMH - Downstream Manhole, Survey Ends - B 1125

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

    216.6 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

Observations (16)

DistanceCodeObservation
216.6TB
84.1TF
4.9CM
204.3TF
184.8TF
65.1TF
0AMHB 1126
266.7CM
0MWM
264.1TF
169.2TF
87.8TF
0MWL
219.8TFA
72.8TF
270.7AMHB 1125

Properties (6)

additional_info
SC345428
custom_field_two
3
customer
LACSD
datetime
2017-07-06T03:17:47-07:00
documentation
PROPIPE
is_lateral_inspection
false