Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 31, 2016, 08:38 AM
  • 05 1090_05 1089_3312016_014731.mp4

Date
03/31/2016
W/O
0557603
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00488
PipeID
P06324
Time
1:38 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0105
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
LAWNDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
20160325MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 1090
Downstream MH
05 1089
Dir. of Survey
Downstream
Length Surveyed
437.9 ft.
Total Length
437.9 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 05 1090 to 05 1089
MH: 05 1090MH: 05 1089downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:40AM4.3 ft. DSGV - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES22.3 ft. MGO - General Observation - 24" VCP68.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"170.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"191.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start268.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"373.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"421.2 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE437.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active437.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish437.9 ft. AMH - Downstream Manhole, Survey Ends - 2:15AM

Observation photos (2)

  • General Observation - 24" VCP

    22.3 ft. - General Observation - 24" VCP

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    191.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
437.9AMH2:15AM
22.3MGO24" VCP
437.5MGOConn. @ Mh, 9 O' Clock. Active
0MWL
4.3DSGV
68.6TFC
421.2FCHAIRLINE
373.1TFC
437.5DAGS
268.1TFC
0MWM
170.4TFC
191.7DAGS
0AMH1:40AM

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2016-03-31T01:38:46-07:00
documentation
MARTIN,MANANES,REVELES,
is_lateral_inspection
false