Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2016, 10:46 AM
  • 05 2494_05 1091_3302016_050256.mp4

Date
03/30/2016
W/O
0557603
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00488
PipeID
P06326
Time
3:46 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0104
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
LAWNDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
20160325MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 1091
Downstream MH
05 2494
Dir. of Survey
Upstream
Length Surveyed
428.9 ft.
Total Length
428.9 ft.
Structural Index
3
Structural Quick
3400
Structural Rating
12
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole 05 1091 to 05 2494
MH: 05 1091MH: 05 2494upstream0 ft. AMH - Upstream Manhole, Survey Ends - 5:35AM0.5 ft. DSGV - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO, Finish0.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish44.5 ft. DSGV - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO, Start53.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT104.5 ft. MGP - General Photograph107.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT107.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE117.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE121.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"222.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active225.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE245.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE252.5 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE259.1 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE323.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start323.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"424.9 ft. MGO - General Observation - 24" VCP428.9 ft. MWL - Water Level, 10 %of cross sectional area428.9 ft. AMH - Downstream Manhole, Survey Begins - 4:55AM428.9 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active428.9 ft. MWM - Water Mark, 40 %of cross sectional area428.9 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active

Observation photos (7)

  • General Observation - 24" VCP

    4 ft. - General Observation - 24" VCP

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    105 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    169.8 ft. - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    183.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    311.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    321.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • General Photograph

    324.4 ft. - General Photograph

Observations (24)

DistanceCodeObservation
183.5FLHAIRLINE
428.4DSGV
428.9AMH5:35AM
105DAGS
0MWL
428.4MGOConn. @ Mh, 9 O' Clock. Active
4MGO24" VCP
375.4FLSLIGHT
321.2FLSLIGHT
428.4DAGS
0AMH4:55AM
0MGOConn. @ Mh, 3 O' Clock. Active
0MWM
311.7FLHAIRLINE
307.6TFC
169.8FSHAIRLINE
105TFC
0MGOConn. @ Mh, 9 O' Clock. Active
324.4MGP
176.4FSHAIRLINE
203.6FLHAIRLINE
384.4DSGV
321.2FLHAIRLINE
206.6TFActive

Properties (6)

custom_field_three
SLIGHT LONG JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2016-03-30T03:46:33-07:00
documentation
MARTIN,MANANES,REVELES,
is_lateral_inspection
false