Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2016, 07:25 AM
  • 05 1095_05 1094_3302016_003806.mp4

Date
03/30/2016
W/O
0557603
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00488
PipeID
P06329
Time
12:25 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0102
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
LAWNDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
20160325MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
05 1095
Downstream MH
05 1094
Dir. of Survey
Downstream
Length Surveyed
323.6 ft.
Total Length
323.6 ft.
Structural Index
2
Structural Quick
513A
Structural Rating
86
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
88
Pipe schematic from manhole 05 1095 to 05 1094
MH: 05 1095MH: 05 1094downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:25AM0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area6 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE12.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H20.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT42.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT42.1 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H48.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"52.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H52.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H59.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - MODERATE85.8 ft. MGO - General Observation - 12" VCP92.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT92.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H109.4 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H112.5 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SLIGHT112.5 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H112.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H125.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT127.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H141.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start150.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open154.8 ft. CC - Crack Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES164.5 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SLIGHT164.5 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - H177.3 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT177.3 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H196.4 ft. BSV - Broken Soil Visible, from 12 to 04 o'clock, within 8 inches of joint: YES - MODERATE FRACTURE228 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H235.1 ft. CC - Crack Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES238 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT247.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H247.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"255.9 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H255.9 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SLIGHT290.6 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SLIGHT290.6 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT293 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H299.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H306.2 ft. FC - Fracture Circumferential, from 09 to 02 o'clock, within 8 inches of joint: YES - H308.9 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H311.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SLIGHT317.3 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT317.3 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H323.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish323.6 ft. AMH - Downstream Manhole, Survey Ends - 1:20AM

Observation photos (4)

  • Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - MODERATE

    59.8 ft. - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - MODERATE

  • General Observation - 12" VCP

    85.8 ft. - General Observation - 12" VCP

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    141.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Broken Soil Visible, from 12 to 04 o'clock, within 8 inches of joint: YES - MODERATE FRACTURE

    196.4 ft. - Broken Soil Visible, from 12 to 04 o'clock, within 8 inches of joint: YES - MODERATE FRACTURE

Observations (47)

DistanceCodeObservation
290.6FCSLIGHT
290.6FCSLIGHT
112.5FCSLIGHT
0AMH12:25AM
112.5FCH
85.8MGO12" VCP
42.1FLSLIGHT
52.4FLH
255.9FCH
109.4FCH
48.8TFC
154.8CC
112.5FLH
92.3FLSLIGHT
196.4BSVMODERATE FRACTURE
141.5DAGS
235.1CC
0MWL
306.2FCH
177.3FLSLIGHT
255.9FCSLIGHT
228FLH
92.3FCH
238FCSLIGHT
125.2FCSLIGHT
293FLH
150.5TFOpen
164.5FCSLIGHT
323.3DAGS
317.3FLSLIGHT
308.9FCH
317.3FCH
59.8FCMODERATE
164.5FCH
127.7FLH
247.7TFC
299.2FLH
52.4FCH
323.6AMH1:20AM
12.3FLH
177.3FCH
0MWM
247.6FCH
20.7FCSLIGHT
6FCHAIRLINE
311.1FCSLIGHT
42.1FCH

Properties (6)

custom_field_three
BROKEN PIPE SOIL VISIBLE=MODERATE FRACTURE
custom_field_two
1
customer
LACSD
datetime
2016-03-30T00:25:00-07:00
documentation
MARTIN,MANANES,REVELES,
is_lateral_inspection
false