Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 29, 2016, 07:45 AM
  • 05 2504_05 1098_3292016_005742.mp4

Date
03/29/2016
W/O
0557603
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00488
PipeID
P06333
Time
12:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0101
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
LAWNDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
20160325MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
05 2504
Downstream MH
05 1098
Dir. of Survey
Downstream
Length Surveyed
311.4 ft.
Total Length
311.4 ft.
Structural Index
3
Structural Quick
3A2A
Structural Rating
58
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
62
Pipe schematic from manhole 05 2504 to 05 1098
MH: 05 2504MH: 05 1098downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active OUTGOING0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active INCOMING0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:45AM0 ft. MWL - Water Level, 10 %of cross sectional area1 ft. MGP - General Photograph - PAPER BUILDUP8 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - HAIRLINE12.3 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H32.6 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H32.6 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - H45.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"45.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H45.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, - H47.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT55.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT55.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H79.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H79.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H84.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H87.9 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - H92.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H100.1 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE100.1 ft. FL - Fracture Longitudinal, at 09 TO 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE112.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT121.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"132.1 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SLIGHT190.9 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SLIGHT211.8 ft. MGO - General Observation - 12" VCP222.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"261.1 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SLIGHT261.1 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SLIGHT291.6 ft. MWL - Water Level, 20 %of cross sectional area295.6 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT295.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT311 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - 60% AT JOINTS HAIRLINE311 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - 15% AT JOINTS HAIRLINE311.4 ft. AMH - Downstream Manhole, Survey Ends - 1:30AM

Observation photos (3)

  • General Photograph - PAPER BUILDUP

    1 ft. - General Photograph - PAPER BUILDUP

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES,  - H

    45.1 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, - H

  • General Observation - 12" VCP

    211.8 ft. - General Observation - 12" VCP

Observations (37)

DistanceCodeObservation
0MGOConn. @ Mh, 3 O' Clock. Active OUTGOING
190.9FCSLIGHT
45.1TFC
311FL60% AT JOINTS HAIRLINE
32.6FCH
45.1FLH
295.6FCSLIGHT
121.4TFC
8FLHAIRLINE
0MGOConn. @ Mh, 9 O' Clock. Active INCOMING
47.1FLSLIGHT
84.1FLH
92.1FLH
79.8FLH
0MWM
222.6TFC
32.6FCH
291.6MWL
1MGPPAPER BUILDUP
311.4AMH1:30AM
132.1FCSLIGHT
0AMH12:45AM
112.5FCSLIGHT
295.6FLSLIGHT
211.8MGO12" VCP
55.1FLSLIGHT
12.3FCH
100.1FCHAIRLINE
261.1FCSLIGHT
311FC15% AT JOINTS HAIRLINE
0MWL
261.1FCSLIGHT
87.9FCH
79.8FLH
45.1FLH
55.3FLH
100.1FLHAIRLINE

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2016-03-29T00:45:11-07:00
documentation
MARTIN,MANANES,REVELES,
is_lateral_inspection
false