Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 14, 2016, 09:30 AM
  • 21 0933_21 0932_3142016_024347.mp4

Date
03/14/2016
W/O
0552361
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00760
PipeID
P16021
Time
2:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0091
Sewer Name
21 CLAREMONT OUTFALL TRUNK
City
POMONA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
10
Purpose
Routine Assessment
Project
20160314MDM_CLAREMONT_OUTFALL_TRUNK
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
21 0933
Downstream MH
21 0932
Dir. of Survey
Downstream
Length Surveyed
693.8 ft.
Total Length
693.8 ft.
Structural Index
3
Structural Quick
473I
Structural Rating
212
O&M Index
3
O&M Quick
3221
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
220
Pipe schematic from manhole 21 0933 to 21 0932
MH: 21 0933MH: 21 0932downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - MH CONN OPEN 9:000 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:35AM2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG15.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT27.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT27.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE27.8 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT38.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT38.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT47.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open48.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT48.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE58.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT65.7 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT70.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT73 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE80.7 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - HAIRLINE80.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - HAIRLINE88.3 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT88.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE88.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT100.8 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT118.5 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - HAIRLINE118.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE126.2 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - HAIRLINE126.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT143.9 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SLIGHT143.9 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - SLIGHT179.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open181.7 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - SLIGHT181.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT191.6 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE191.6 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - SLIGHT197.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN209.4 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES - SLIGHT209.4 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT212.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open219.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT219.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT261.7 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT272.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT294.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG294.5 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT294.5 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT304.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT311.8 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - HAIRLINE315.9 ft. SAM - Surface Aggregate Missing, from 09 to 12 o'clock, within 8 inches of joint: NO318 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open321.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG329.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT335.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"342.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT352.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT376.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE376.2 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active378.1 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES - SLIGHT389.7 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - SLIGHT392.8 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - SLIGHT402.7 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT414.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT421.4 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 3", 1" - Open435.4 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES - SLIGHT435.4 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT448.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVEREAGG465.1 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - SLIGHT489.2 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 6", 6" - ACTIVE-MISSING PIPE SOIL VISIBLE489.2 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 6" - Active-MISSING PIE SOIL VISIBLE489.5 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SLIGHT489.5 ft. MGP - General Photograph490 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT490 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT500.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT500.1 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT512.2 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SLIGHT534.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT554.9 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT570.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"573.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN580 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT602.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT630 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SLIGHT635.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT669.3 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - MODERATE671.5 ft. FC - Fracture Circumferential, from 09 to 02 o'clock, within 8 inches of joint: YES - SLIGHT673.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT676.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT679.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT681.3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT684 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT693.4 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG693.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG693.8 ft. AMH - Downstream Manhole, Survey Ends - 4:20AM

Observation photos (12)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE

    27.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    294.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 09 to 12 o'clock, within 8 inches of joint: NO

    315.9 ft. - Surface Aggregate Missing, from 09 to 12 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    321.1 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVEREAGG

    448.3 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVEREAGG

  • Tap Break-In Defective, at 10 o'clock, -,  , within 8 inches of joint: YES, 6", 6" - ACTIVE-MISSING PIPE SOIL VISIBLE

    489.2 ft. - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 6", 6" - ACTIVE-MISSING PIPE SOIL VISIBLE

  • Tap Break-In Defective, at 10 o'clock, -,  , within 8 inches of joint: YES, 6" - Active-MISSING PIE SOIL VISIBLE

    489.2 ft. - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 6" - Active-MISSING PIE SOIL VISIBLE

  • General Photograph

    489.5 ft. - General Photograph

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

    580 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

    602.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

  • Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - MODERATE

    669.3 ft. - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - MODERATE

Observations (94)

DistanceCodeObservation
272.3FLSLIGHT
534.7FLSLIGHT
38.5FLSLIGHT
681.3FCSLIGHT
376.2FLHAIRLINE
392.8FLSLIGHT
126.2FLHAIRLINE
554.9FCSLIGHT
570.8TFC
402.7FLSLIGHT
630FMSLIGHT
676.2FLSLIGHT
294.5SAPSEVERE AGG
179.8TFOpen
197.7TBOPEN
315.9SAM
489.5FCSLIGHT
143.9FCSLIGHT
342.3FLSLIGHT
118.5FLHAIRLINE
2SAPSEVERE AGG
465.1FLSLIGHT
671.5FCSLIGHT
48.2FLSLIGHT
580FMSLIGHT
304.4FLSLIGHT
0MWM
635.2FCSLIGHT
0MGOMH CONN OPEN 9:00
693.4SAMSEVERE AGG
679.2FCSLIGHT
435.4FLSLIGHT
0MWL
389.7FLSLIGHT
311.8FLHAIRLINE
0AMH2:35AM
335.5TFC
212.7TFOpen
27.8FLSLIGHT
209.4FLSLIGHT
27.8SAPSEVERE
219.3FCSLIGHT
27.8FLSLIGHT
219.3FLSLIGHT
693.8AMH4:20AM
448.3SAMSEVEREAGG
673.9FMSLIGHT
500.1FLSLIGHT
318TBOpen
512.2FCSLIGHT
143.9FCSLIGHT
261.7FLSLIGHT
684FCSLIGHT
181.7FLSLIGHT
191.6FCHAIRLINE
489.2TBDACTIVE-MISSING PIPE SOIL VISIBLE
80.7FLHAIRLINE
126.2FLSLIGHT
352.7FLSLIGHT
47.7TBOpen
294.5FLSLIGHT
414.9FLSLIGHT
376.2TBActive
321.1SAMSEVERE AGG
88.3FLSLIGHT
58.6FLSLIGHT
294.5FLSLIGHT
48.2FLHAIRLINE
573.7TBOPEN
191.6FCSLIGHT
669.3FCMODERATE
118.5FLHAIRLINE
378.1FLSLIGHT
209.4FLSLIGHT
602.4FMSLIGHT
73FLHAIRLINE
329.5FLSLIGHT
70.9FLSLIGHT
100.8FLSLIGHT
693.4SAPSEVERE AGG
490FLSLIGHT
489.2TBDActive-MISSING PIE SOIL VISIBLE
80.7FLHAIRLINE
500.1FLSLIGHT
88.3FCHAIRLINE
38.6FLSLIGHT
88.3FLSLIGHT
421.4TBIOpen
490FCSLIGHT
65.7FCSLIGHT
15.6FLSLIGHT
435.4FLSLIGHT
489.5MGP
181.7FLSLIGHT

Properties (6)

custom_field_three
MISSING SEVERE AGG- DEFECT-CONN WITH SOIL VISIBLE
custom_field_two
2
customer
LACSD
datetime
2016-03-14T02:30:00-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false