Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 9, 2016, 09:35 PM
  • C 0482_C 0481_392016_133643.mp4

Date
03/09/2016
W/O
0547102
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00132
PipeID
P09732
Time
1:35 PM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7073
Sewer Name
C JOINT OUTFALL C - UNIT 6C RENOVATION*
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
20160309AM_JOINT_OUTFALL_C_UNIT_6C_RENOVATION
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Upstream MH
C 0481
Downstream MH
C 0482
Dir. of Survey
Upstream
Length Surveyed
545.6 ft.
Total Length
545.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole C 0481 to C 0482
MH: C 0481MH: C 0482upstream0 ft. AMH - Upstream Manhole, Survey Ends - 1:58 PM1 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 12 O'CLOCK4.2 ft. MGO - General Observation - PEELING JOINT MATERIAL6.3 ft. MGO - General Observation - PEELING JOINT MATERIAL237.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4" - OPEN319 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 4"415.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4" - OPEN545.6 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK545.6 ft. MWL - Water Level, 35 %of cross sectional area545.6 ft. AMH - Downstream Manhole, Survey Begins - 1:35 PM545.6 ft. MWM - Water Mark, 40 %of cross sectional area

Observation photos (4)

  • Downstream Manhole, Survey Begins - 1:35 PM

    0 ft. - Downstream Manhole, Survey Begins - 1:35 PM

  • Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4" - OPEN

    308.3 ft. - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4" - OPEN

  • General Observation - PEELING JOINT MATERIAL

    539.3 ft. - General Observation - PEELING JOINT MATERIAL

  • General Observation - PEELING JOINT MATERIAL

    541.4 ft. - General Observation - PEELING JOINT MATERIAL

Observations (11)

DistanceCodeObservation
541.4MGOPEELING JOINT MATERIAL
0MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
226.6TFA
308.3TFOPEN
0MWL
0AMH1:35 PM
544.6MGOACTIVE CONN. INSIDE THE MH. @ 12 O'CLOCK
539.3MGOPEELING JOINT MATERIAL
0MWM
545.6AMH1:58 PM
130.3TFOPEN

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2016-03-09T13:35:03-08:00
documentation
MIRANDA, FRANKLIN, SHADLER, MIRABAL
is_lateral_inspection
false