Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 4, 2016, 08:40 AM
  • 02 1357_02 1356_342016_004601.mp4

Date
03/04/2016
W/O
0541751
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00277
PipeID
P03880
Time
12:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0080
Sewer Name
02 JANE STREET BRANCH TRUNK
City
LOS ANGLES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
11A
Purpose
Routine Assessment
Project
20160302MDM_JANE_STREET_BRANCH_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
02 1357
Downstream MH
02 1356
Dir. of Survey
Downstream
Length Surveyed
333.8 ft.
Total Length
333.8 ft.
Structural Index
2
Structural Quick
4132
Structural Rating
24
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
24
Pipe schematic from manhole 02 1357 to 02 1356
MH: 02 1357MH: 02 1356downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:40AM7 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE10 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H11 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"11.4 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H12.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - H12.3 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H13.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"20.9 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE FRACTURES AT JOINTS20.9 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H20.9 ft. FL - Fracture Longitudinal, at 09 TO 03 o'clock, within 8 inches of joint: YES, Start - HAIELINE FRACTURES AT JOINTS99 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active101.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"148.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT197.4 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - SLIGHT198.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"201.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active235.9 ft. MWL - Water Level, 50 %of cross sectional area309.7 ft. MGP - General Photograph - 12" VCP314.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"317.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"333.5 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - 90% HAIRLINE AT JOINTS333.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - 30% HAIRLINE AT JOINTS333.8 ft. AMH - Downstream Manhole, Survey Ends - 1:25AM

Observation photos (1)

  • General Photograph - 12" VCP

    309.7 ft. - General Photograph - 12" VCP

Observations (26)

DistanceCodeObservation
309.7MGP12" VCP
99TFActive
333.5FC90% HAIRLINE AT JOINTS
235.9MWL
7FCHAIRLINE
0MWM
148.7FCSLIGHT
12.3FMH
11TFC
0MWL
197.4FCSLIGHT
20.9FCHAIRLINE FRACTURES AT JOINTS
12.3FLH
198.6TFC
0AMH12:40AM
317.1TFC
333.5FL30% HAIRLINE AT JOINTS
20.9FCH
201.8TFActive
10FCH
101.4TFC
13.2TFC
333.8AMH1:25AM
20.9FLHAIELINE FRACTURES AT JOINTS
11.4FCH
314.5TFC

Properties (6)

custom_field_three
HAIRLINE SPRIAL JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2016-03-04T00:40:00-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false