Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2015, 04:36 PM
  • 02 0164_02 0163_1292015_085344.mp4

Date
12/09/2015
W/O
0536410
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00251
PipeID
P02467
Time
8:36 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7011
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
20151204AM_DOWNEY_BELLFLOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
02 0164
Downstream MH
02 0163
Dir. of Survey
Downstream
Length Surveyed
336.2 ft.
Total Length
336.2 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 02 0164 to 02 0163
MH: 02 0164MH: 02 0163downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 8:53 AM0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK0 ft. MGO - General Observation - ACTIVE DROP CONN. INSIDE THE MH. @ 09 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start23 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY THROUGHOUT62.7 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES68.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES107.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN110.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN161.9 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - CAPPED, CRACKED164.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"180.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"219.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN222.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN249.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"323.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SPORADICALLY THROUGHOUT332.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish332.2 ft. MGO - General Observation - DEBRIS THROUGHOUT THE REACH333.4 ft. MGO - General Observation - ROACHES INSIDE THE MH.334.4 ft. MGO - General Observation - CAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK334.8 ft. MGO - General Observation - CAPPED CONN. INSIDE THE MH. @ 09 O'CLOCK336.2 ft. AMH - Downstream Manhole, Survey Ends - 9:28 AM

Observation photos (1)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY THROUGHOUT

    23 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY THROUGHOUT

Observations (25)

DistanceCodeObservation
332.2DAGS
0MWL
249.4TFC
333.4MGOROACHES INSIDE THE MH.
164.9TFC
62.7CL
0AMH8:53 AM
68.7CL
334.8MGOCAPPED CONN. INSIDE THE MH. @ 09 O'CLOCK
110.2TFOPEN
161.9TFDCAPPED, CRACKED
23CLSPORADICALLY THROUGHOUT
107.4TFOPEN
180.1TFC
222.4TFOPEN
0MGOROACHES INSIDE THE MH.
2DAGS
0MWM
332.2MGODEBRIS THROUGHOUT THE REACH
0MGOCAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK
334.4MGOCAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK
336.2AMH9:28 AM
0MGOACTIVE DROP CONN. INSIDE THE MH. @ 09 O'CLOCK
323.6CLSPORADICALLY THROUGHOUT
219.4TFOPEN

Properties (6)

custom_field_three
CONTINUOUS LONGITUDINAL CRACKS
custom_field_two
2
customer
LACSD
datetime
2015-12-09T08:36:12-08:00
documentation
MIRANDA, FRANKLIN, SHADLER, MIRABAL
is_lateral_inspection
false