Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 8, 2015, 04:26 PM
  • 02 0161_02 0160_1282015_085131.mp4

Date
12/08/2015
W/O
0536410
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00251
PipeID
P02464
Time
8:26 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7009
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
20151204AM_DOWNEY_BELLFLOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
02 0161
Downstream MH
02 0160
Dir. of Survey
Downstream
Length Surveyed
360.8 ft.
Total Length
360.8 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2600
O&M Rating
12
Overall Index
2
Overall Quick
Overall Rating
17
Pipe schematic from manhole 02 0161 to 02 0160
MH: 02 0161MH: 02 0160downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 8:50 AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK0 ft. MGO - General Observation - CAPPED CONN. INSIDE THE MH. @ 09 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start95.6 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"98 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"101.2 ft. TBI - Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: YES, 4", 2" - ACTIVE136.5 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES153.3 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, POSSIBLY BROKEN156.2 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4" - ACTIVE, BROKEN205.1 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 4" - ACTIVE, BROKEN231.9 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 4"242.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN254.3 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 4"260.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN302.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 4"345.4 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, BROKEN353.6 ft. CS - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES358.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish360.1 ft. MGO - General Observation - CAPPED CONN. INSIDE THE MH. @ 09 O'CLOCK360.1 ft. MGO - General Observation - ROACHES INSIDE THE MH.360.1 ft. MGO - General Observation - CAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK360.8 ft. AMH - Downstream Manhole, Survey Ends - 9:24 AM

Observation photos (5)

  • Upstream Manhole, Survey Begins - 8:50 AM

    0 ft. - Upstream Manhole, Survey Begins - 8:50 AM

  • Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: YES, 4", 2" - ACTIVE

    101.2 ft. - Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: YES, 4", 2" - ACTIVE

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4" - ACTIVE, BROKEN

    156.2 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4" - ACTIVE, BROKEN

  • Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 4" - ACTIVE, BROKEN

    205.1 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 4" - ACTIVE, BROKEN

  • Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, BROKEN

    345.4 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, BROKEN

Observations (25)

DistanceCodeObservation
153.3TFDOPEN, POSSIBLY BROKEN
302.8TFA
360.1MGOCAPPED CONN. INSIDE THE MH. @ 09 O'CLOCK
0MWL
260.7TFOPEN
101.2TBIACTIVE
0AMH8:50 AM
0MWM
0MGOCAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK
98TFC
360.1MGOROACHES INSIDE THE MH.
254.3TFA
95.6TFA
360.8AMH9:24 AM
231.9TBA
156.2TFDACTIVE, BROKEN
205.1TFDACTIVE, BROKEN
242.3TFOPEN
2DAGS
0MGOCAPPED CONN. INSIDE THE MH. @ 09 O'CLOCK
136.5CM
360.1MGOCAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK
358.5DAGS
345.4TFDOPEN, BROKEN
353.6CS

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-12-08T08:26:29-08:00
documentation
MIRANDA, FRANKLIN, SHADLER, MIRABAL
is_lateral_inspection
false