Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 4, 2015, 05:12 PM
  • 02 0168_02 0167_1242015_095836.mp4

Date
12/04/2015
W/O
0536410
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00251
PipeID
P02471
Time
9:12 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7007
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
20151204AM_DOWNEY_BELLFLOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0168
Downstream MH
02 0167
Dir. of Survey
Downstream
Length Surveyed
522.4 ft.
Total Length
522.4 ft.
Structural Index
2
Structural Quick
3423
Structural Rating
20
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
22
Pipe schematic from manhole 02 0168 to 02 0167
MH: 02 0168MH: 02 0167downstream0 ft. AMH - Upstream Manhole, Survey Begins - 9:57 AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE DROP CONN. INSIDE THE MH. @ 09 O'CLOCK0 ft. MGO - General Observation - MOUSE IN THE LINE49.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"52.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"84.7 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES104.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"107.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"109 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES145.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES150.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"153.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - UNKNOWN175.8 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES207.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"211.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"253.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6" - OPEN256.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"292 ft. CM - Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES294.8 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES302.7 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"305.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN363.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"366.6 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 4"413 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"415.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"461 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"464.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"465.7 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES475.4 ft. DAR - Deposits Attached Ragging, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES517.4 ft. CC - Crack Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES517.4 ft. CC - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES520.3 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH521.1 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK521.2 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK521.3 ft. MGO - General Observation - ROACHES INSIDE THE MH.522.4 ft. AMH - Downstream Manhole, Survey Ends - 10:44 AM

Observation photos (3)

  • General Observation - MOUSE IN THE LINE

    0 ft. - General Observation - MOUSE IN THE LINE

  • Deposits Attached Ragging, 10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES

    475.4 ft. - Deposits Attached Ragging, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

  • General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK

    521.2 ft. - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK

Observations (38)

DistanceCodeObservation
207.8TFC
109CM
517.4CC
0AMH9:57 AM
153.1TFUNKNOWN
461TFA
522.4AMH10:44 AM
0MWL
0MWM
145.8CM
475.4DAR
413TFC
521.1MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
253.8TFOPEN
175.8CL
292CM
415.5TFC
211.1TFC
465.7CL
150.1TFC
0MGOACTIVE DROP CONN. INSIDE THE MH. @ 09 O'CLOCK
49.4TFC
305.6TFOPEN
521.3MGOROACHES INSIDE THE MH.
363.6TFC
104.4TFC
520.3MGOSLIGHT GREASE THROUGHOUT THE REACH
464.2TFC
302.7TFA
294.8CL
521.2MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
517.4CC
0MGOMOUSE IN THE LINE
107.5TFC
366.6TFA
256.8TFC
52.6TFC
84.7CM

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-12-04T09:12:35-08:00
documentation
MIRANDA, FRANKLIN, SHADLER, MIRABAL
is_lateral_inspection
false