Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 4, 2015, 05:08 PM
  • 02 0169_02 0168_1242015_092228.mp4

Date
12/04/2015
W/O
0536410
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00251
PipeID
P02472
Time
9:08 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7007
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
20151204AM_DOWNEY_BELLFLOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0169
Downstream MH
02 0168
Dir. of Survey
Downstream
Length Surveyed
361.3 ft.
Total Length
361.3 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 02 0169 to 02 0168
MH: 02 0169MH: 02 0168downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 9:22 AM20.4 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES32.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start34.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"37.4 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, CRACKED, 20% BLOCKED48.1 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES82.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"85.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"102.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES130.8 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, 10% BLOCKED133.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"181.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6" - OPEN185.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"229.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"232.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"294 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"297.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"352.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"355.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"359.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish360.3 ft. MGO - General Observation - ACTIVE DROP CONN. INSIDE THE MH. @ 09 O'CLOCK361.3 ft. AMH - Downstream Manhole, Survey Ends - 9:53 AM

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    32.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, CRACKED, 20% BLOCKED

    37.4 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, CRACKED, 20% BLOCKED

Observations (25)

DistanceCodeObservation
130.8TFDOPEN, 10% BLOCKED
355.1TFC
37.4TFDACTIVE, CRACKED, 20% BLOCKED
232.9TFC
185.1TFC
360.3MGOACTIVE DROP CONN. INSIDE THE MH. @ 09 O'CLOCK
34.3TFC
20.4CL
0MWM
359.1DAGS
0MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
0MWL
294TFC
102.1CL
82.5TFC
181.7TFOPEN
48.1CL
297.1TFC
352.2TFC
85.5TFC
133.7TFC
0AMH9:22 AM
32.7DAGS
361.3AMH9:53 AM
229.8TFC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-12-04T09:08:58-08:00
documentation
MIRANDA, FRANKLIN, SHADLER, MIRABAL
is_lateral_inspection
false