Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2020, 12:30 PM
  • 02 2289_02 1740_12122020_043517.mp4

Date
12/12/2020
W/O
0865140
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00254
PipeID
P08464
Time
4:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1670
Sewer Name
02 DOWNEY-BELLFLOWER EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
15
Purpose
Routine Assessment
Project
20201210MDM_DOWNEY_BELLFLOWER_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 2289
Downstream MH
02 1740
Dir. of Survey
Downstream
Length Surveyed
224.2 ft.
Total Length
224.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 02 2289 to 02 1740
MH: 02 2289MH: 02 1740downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:40AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active65.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open166.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE167.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open214.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open224.2 ft. AMH - Downstream Manhole, Survey Ends - 4:55AM

Observations (9)

DistanceCodeObservation
0AMH4:40AM
0MWL
166.5FLHAIRLINE
65.6TFOpen
214.8TFOpen
224.2AMH4:55AM
167.3TFOpen
0MWM
0MGOConn. @ Mh, 3 O' Clock. Active

Properties (6)

custom_field_three
HAIRLINE LONG FRACTURE
custom_field_two
4
customer
LACSD
datetime
2020-12-12T04:30:24-08:00
documentation
MARTIN,OLIVER 111,RUVALCABA,CASTILLO
is_lateral_inspection
false