Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 10, 2020, 11:20 AM
  • 02 1756_02 1755A_12102020_032508.mp4

Date
12/10/2020
W/O
0865140
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00254
PipeID
P04100
Time
3:20 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1663
Sewer Name
02 DOWNEY-BELLFLOWER EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
15
Purpose
Routine Assessment
Project
20201210MDM_DOWNEY_BELLFLOWER_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
02 1756
Downstream MH
02 1755A
Dir. of Survey
Downstream
Length Surveyed
82.8 ft.
Total Length
82.8 ft.
Structural Index
2
Structural Quick
3125
Structural Rating
13
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
15
Pipe schematic from manhole 02 1756 to 02 1755A
MH: 02 1756MH: 02 1755Adownstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. STUB0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 3:25AM6.2 ft. FC - Fracture Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES - SLIGHT11.4 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SLIGHT39.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL48 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL56.3 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL56.3 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SL61.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start82.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish82.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active82.8 ft. AMH - Downstream Manhole, Survey Ends - 3:25AM

Observations (15)

DistanceCodeObservation
48FCSL
56.3FCSL
82.6DAGS
11.4FCSLIGHT
56.3FLSL
82.6MGOConn. @ Mh, 3 O' Clock. Active
0MGOConn. @ Mh, 3 O' Clock. STUB
82.8AMH3:25AM
0MWL
61.7DAGS
39.9FCSL
0MWM
6.2FCSLIGHT
0MGOConn. @ Mh, 9 O' Clock. Active
0AMH3:25AM

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2020-12-10T03:20:55-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false