Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 10, 2020, 09:10 AM
  • 02 1757_02 1756_12102020_023206.mp4

Date
12/10/2020
W/O
0865140
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00254
PipeID
P04101
Time
1:10 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1663
Sewer Name
02 DOWNEY-BELLFLOWER EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
15
Purpose
Routine Assessment
Project
20201210MDM_DOWNEY_BELLFLOWER_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
02 1757
Downstream MH
02 1756
Dir. of Survey
Downstream
Length Surveyed
352 ft.
Total Length
352 ft.
Structural Index
2
Structural Quick
332D
Structural Rating
61
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
65
Pipe schematic from manhole 02 1757 to 02 1756
MH: 02 1757MH: 02 1756downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. STUB0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:30AM1 ft. MGO - General Observation - THIS REACH(MH#1755 TO MH#1754)4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT10.2 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL12.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES14.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open17.1 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL17.1 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL25.2 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL36.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start53.6 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL61.8 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - H61.8 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H73.8 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL94.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H106.4 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL118.5 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL138.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES138.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL151.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open154.5 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - H162.3 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES - H174.8 ft. FC - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES - SL182.7 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H211.2 ft. FC - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES - SL215.1 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES215.1 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL223.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL231.4 ft. FC - Fracture Circumferential, from 12 to 05 o'clock, within 8 inches of joint: YES, - SL272.1 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL276.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open282.9 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - H283 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H307 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL311.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL347.6 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL351.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish351.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active351.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active352 ft. AMH - Downstream Manhole, Survey Ends - 3:15AM

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES

    12.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES

Observations (43)

DistanceCodeObservation
211.2FCSL
36.4DAGS
162.3FLH
1MGOTHIS REACH(MH#1755 TO MH#1754)
73.8FCSL
154.5FLH
215.1FC
307FCSL
351.5DAGS
0MGOConn. @ Mh, 3 O' Clock. STUB
311.1FCSL
272.1FCSL
61.8FCH
215.1FCSL
347.6FCSL
351.5MGOConn. @ Mh, 9 O' Clock. Active
282.9FCH
182.7FLH
25.2FCSL
352AMH3:15AM
53.6FCSL
351.5MGOConn. @ Mh, 3 O' Clock. Active
0MWL
106.4FCSL
4FCSLIGHT
0MWM
0AMH2:30AM
223.4FCSL
138.8FC
94.4FCH
174.8FCSL
138.8FCSL
12.3DAGS
118.5FCSL
231.4FCSL
14.7TFOpen
10.2FCSL
17.1FCSL
283FCH
61.8FCH
151.9TFOpen
276.5TFOpen
17.1FCSL

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2020-12-10T01:10:54-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false