Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2020, 07:50 AM
  • D 0052_D-JOINT_12112020_000925.mp4

Date
12/11/2020
W/O
0864850
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00152
PipeID
P21294
Time
11:50 PM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1668
Sewer Name
D JOINT OUTFALL D - UNIT 2B
City
DARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
24
Purpose
Capital Improvement Program Assesment
Project
20201212MDM_JOINT_OUTFALL_D_UNIT_2B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Upstream MH
D 0052
Downstream MH
D-JOINT
Dir. of Survey
Downstream
Length Surveyed
7.8 ft.
Total Length
7.8 ft.
Structural Index
5
Structural Quick
5141
Structural Rating
9
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
14
Pipe schematic from manhole D 0052 to D-JOINT
MH: D 0052MH: D-JOINTdownstream0 ft. MWL - Water Level, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:05AM0 ft. MWM - Water Mark, 80 %of cross sectional area2 ft. MGP - General Photograph - LONG & CIRCUM REBAR MISSING2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGP - General Photograph - HANGING LONG REBAR2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR BROKEN MISSING7.5 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG7.5 ft. MGP - General Photograph - ZOOM DOWNSTREAM TO SIPHON LOOKING AREA7.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR CORRODED & MISSING7.8 ft. AMH - Downstream Manhole, Survey Ends - 12:20AM

Observation photos (5)

  • General Photograph - LONG & CIRCUM REBAR MISSING

    2 ft. - General Photograph - LONG & CIRCUM REBAR MISSING

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Photograph - HANGING LONG REBAR

    2 ft. - General Photograph - HANGING LONG REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR BROKEN  MISSING

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR BROKEN MISSING

  • General Photograph - ZOOM DOWNSTREAM TO SIPHON  LOOKING AREA

    7.5 ft. - General Photograph - ZOOM DOWNSTREAM TO SIPHON LOOKING AREA

Observations (11)

DistanceCodeObservation
2MGPLONG & CIRCUM REBAR MISSING
0MWL
0AMH12:05AM
7.5SAMSEVERE AGG
2SAMSEVERE AGG
0MWM
7.8AMH12:20AM
7.5MGPZOOM DOWNSTREAM TO SIPHON LOOKING AREA
2MGPHANGING LONG REBAR
2SRCLONG & CIRCUM REBAR BROKEN MISSING
7.5SRCLONG & CIRCUM REBAR CORRODED & MISSING

Properties (7)

custom_field_three
LONG & CIRCUM REBAR CORRODED & MISSING & BROKEN
custom_field_two
1
customer
LACSD
datetime
2020-12-11T23:50:08-08:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false
year_laid
19970821